← Illinois

Tap water quality report

Pana

EPA monitoring tested this supplier for 108 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
20
detected
5,800
people served
131
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Christian

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

131
health-based violations
291
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0052 µg/L 1/4 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Dichloroacetic Acid
30.24 µg/L
No EPA limit set
worst single sample: 55 µg/L
79/79 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
54.21 µg/L 90%
of the EPA limit 60 µg/L
worst single sample: 105 µg/L
79/79 SYR4 2012–2019
Bromodichloromethane
11.2915 µg/L
No EPA limit set
worst single sample: 16 µg/L
78/78 SYR4 2012–2019
Chloroform
77.831 µg/L
No EPA limit set
worst single sample: 99.3 µg/L
78/78 SYR4 2012–2019
TTHM
95.0845 µg/L 119%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 113.5 µg/L
78/78 SYR4 2012–2019
Trichloroacetic Acid
22.59 µg/L
No EPA limit set
worst single sample: 44.8 µg/L
78/79 SYR4 2012–2019
Dibromochloromethane
3.6195 µg/L
No EPA limit set
worst single sample: 5.188 µg/L
76/78 SYR4 2012–2019
Copper
26.8 µg/L 2.1%
of the EPA limit 1300 µg/L
worst single sample: 73 µg/L
25/40 SYR4 2014–2017
Lead
0.0026 mg/L 17%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Nitrate
1600 µg/L 16%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Dibromoacetic Acid
1.5 µg/L
No EPA limit set
15/79 SYR4 2012–2019
Monobromoacetic Acid
7.8965 µg/L
No EPA limit set
worst single sample: 9.97 µg/L
12/79 SYR4 2012–2019
Barium
32.3 µg/L 1.6%
of the EPA limit 2000 µg/L
worst single sample: 33 µg/L
8/8 SYR4 2012–2019
Fluoride
1212.5 µg/L 30%
of the EPA limit 4000 µg/L
worst single sample: 1230 µg/L
8/8 SYR4 2012–2019
Lead
13.75 µg/L 92%
of the EPA limit 15 µg/L
worst single sample: 19 µg/L
8/40 SYR4 2014–2017
Monochloroacetic Acid
4.6635 µg/L
No EPA limit set
worst single sample: 5.5 µg/L
8/79 SYR4 2012–2019
Nitrate-Nitrite
1253 µg/L 13%
of the EPA limit 10000 µg/L
worst single sample: 1300 µg/L
2/2 SYR4 2015–2018
Arsenic
1 µg/L 10%
of the EPA limit 10 µg/L
1/8 SYR4 2012–2019
Combined Radium (-226 And -228)
1.19 pCi/L 24%
of the EPA limit 5 pCi/L
1/1 SYR4 2015
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PASTER, NATHAN
Phone
217-562-3626
Email
[email protected]

Frequently asked questions about Pana

Is Pana tap water safe to drink?

EPA monitoring detected 20 contaminants in Pana's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Pana's water?

EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Pana serve?

Pana reports serving 5,800 people in Illinois, per its EPA record.

Has Pana had any water quality violations?

The EPA has 291 violations on file for Pana, of which 131 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.