Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Unaddressed | 2025-07-01 |
| MR | Monitoring | Unaddressed | 2025-07-01 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Resolved | 2012-01-01 → 2012-03-31 |
| MR | Monitoring | Archived | 1995-08-01 → 1995-08-31 |
| MR | Monitoring | Archived | 1995-08-01 → 1995-08-31 |
| MR | Monitoring | Archived | 1995-08-01 → 1995-08-31 |
| MR | Monitoring | Archived | 1977-06-30 → 1981-06-29 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 9100 µg/L 91% of the EPA limit 10000 µg/L
worst single sample: 9900 µg/L | 134/138 | SYR4 | 2012–2019 |
| Copper | 2016 µg/L 155% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 3800 µg/L | 125/132 | SYR4 | 2012–2019 |
| Lead | 8.215 µg/L 55% of the EPA limit 15 µg/L
worst single sample: 14.8 µg/L | 60/132 | SYR4 | 2012–2019 |
| Lead | 0.0018 mg/L 12% of the EPA limit 0.0150 mg/L | 26/26 | LCR | 2026 |
| Nitrate-Nitrite | 8315 µg/L 83% of the EPA limit 10000 µg/L
worst single sample: 8570 µg/L | 16/16 | SYR4 | 2012–2018 |
| Bromodichloromethane | 1.86 µg/L No EPA limit set
worst single sample: 1.92 µg/L | 7/7 | SYR4 | 2014–2019 |
| Bromoform | 4.215 µg/L No EPA limit set
worst single sample: 4.32 µg/L | 7/7 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 2.286 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 7/7 | SYR4 | 2014–2019 |
| Dibromochloromethane | 3.882 µg/L No EPA limit set
worst single sample: 3.9 µg/L | 7/7 | SYR4 | 2014–2019 |
| TTHM | 10.161 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 10.23 µg/L | 7/7 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 2.286 µg/L 3.8% of the EPA limit 60 µg/L
worst single sample: 2.4 µg/L | 7/7 | SYR4 | 2014–2019 |
| Barium | 127 µg/L 6.4% of the EPA limit 2000 µg/L
worst single sample: 130 µg/L | 3/3 | SYR4 | 2012–2018 |
| Chloroform | 0.6676 µg/L No EPA limit set
worst single sample: 0.6760 µg/L | 3/7 | SYR4 | 2014–2019 |
| Fluoride | 1175 µg/L 29% of the EPA limit 4000 µg/L
worst single sample: 1190 µg/L | 3/3 | SYR4 | 2012–2018 |
| Selenium | 5.325 µg/L 11% of the EPA limit 50 µg/L
worst single sample: 5.5 µg/L | 2/3 | SYR4 | 2012–2018 |
| Lithium | 20 µg/L No EPA limit set | 2/2 | UCMR-5 | 2023 |
| Arsenic | 1.3 µg/L 13% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2012–2018 |
| Chromium | 5.1 µg/L 5.1% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 0.3080 pCi/L 6.2% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Mill Creek Pwd
Is Mill Creek Pwd tap water safe to drink?
EPA monitoring detected 19 contaminants in Mill Creek Pwd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mill Creek Pwd's water?
EPA monitoring detected Nitrate, Copper, Lead, Lead, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does Mill Creek Pwd serve?
Mill Creek Pwd reports serving 5,755 people in Illinois, per its EPA record.
Has Mill Creek Pwd had any water quality violations?
The EPA has 8 violations on file for Mill Creek Pwd, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.