Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2015-09-01 → 2015-09-30 |
| MCL | Health-based | Archived | 2015-09-01 → 2015-09-30 |
| MCL | Health-based | Archived | 1995-08-01 → 1995-08-31 |
| MCL | Health-based | Archived | 1995-08-01 → 1995-08-31 |
| MCL | Health-based | Archived | 1995-02-01 → 1995-02-28 |
| MCL | Health-based | Archived | 1994-12-01 → 1994-12-31 |
| MCL | Health-based | Archived | 1993-08-01 → 1993-08-31 |
| MR | Monitoring | Resolved | 2016-10-01 → 2016-12-31 |
| MR | Monitoring | Resolved | 2016-10-01 → 2016-12-31 |
| MR | Monitoring | Resolved | 2016-10-01 → 2016-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 3580 µg/L 36% of the EPA limit 10000 µg/L
worst single sample: 3620 µg/L | 44/46 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2023 |
| TTHM | 46.1275 µg/L 58% of the EPA limit 80 µg/L
worst single sample: 69 µg/L | 8/9 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1900 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 1910 µg/L | 6/6 | SYR4 | 2013–2018 |
| Arsenic | 2 µg/L 20% of the EPA limit 10 µg/L | 2/2 | SYR4 | 2019 |
| Barium | 295.5 µg/L 15% of the EPA limit 2000 µg/L
worst single sample: 300 µg/L | 2/2 | SYR4 | 2019 |
| Combined Uranium | 1.795 µg/L 6% of the EPA limit 30 µg/L
worst single sample: 1.8 µg/L | 2/2 | SYR4 | 2014 |
| Fluoride | 439.5 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 440 µg/L | 2/2 | SYR4 | 2019 |
| Gross Alpha, Excl. Radon And U | 3.4531 pCi/L 23% of the EPA limit 15 pCi/L
worst single sample: 3.498 pCi/L | 2/3 | SYR4 | 2013–2014 |
| Combined Radium (-226 And -228) | 0.6600 pCi/L 13% of the EPA limit 5 pCi/L | 1/3 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.8000 µg/L 13% of the EPA limit 6 µg/L | 1/4 | SYR4 | 2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Wendell City of
Is Wendell City of tap water safe to drink?
EPA monitoring detected 11 contaminants in Wendell City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wendell City of's water?
EPA monitoring detected Nitrate, Lead, TTHM, Nitrate-Nitrite, Arsenic, and others. The full list with the level and data source for each is above.
How many people does Wendell City of serve?
Wendell City of reports serving 3,000 people in Idaho, per its EPA record.
Has Wendell City of had any water quality violations?
The EPA has 70 violations on file for Wendell City of, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.