← Iowa

Tap water quality report

Altoona Water Supply

EPA monitoring tested this supplier for 90 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

90
contaminants tested
19
detected
19,565
people served
17
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Polk

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

17
health-based violations
73
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2024-07-01 → 2024-09-30
MCL Health-based Archived 2024-07-01 → 2024-09-30
MCL Health-based Archived 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2001-07-01 → 2002-06-30
MCL Health-based Resolved 2001-07-01 → 2002-06-30
MCL Health-based Resolved 2001-07-01 → 2002-06-30
MCL Health-based Resolved 1992-10-01 → 1992-10-31
MCL Health-based Resolved 1992-10-01 → 1992-10-31
MCL Health-based Resolved 1992-10-01 → 1992-10-31
MCL Health-based Resolved 1992-10-01 → 1992-10-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
604.05 µg/L 46%
of the EPA limit 1300 µg/L
worst single sample: 738 µg/L
90/90 SYR4 2013–2019
Combined Radium (-226 And -228)
4.455 pCi/L 89%
of the EPA limit 5 pCi/L
worst single sample: 4.6 pCi/L
50/50 SYR4 2012–2019
Nitrate
800 µg/L 8%
of the EPA limit 10000 µg/L
40/48 SYR4 2012–2019
Dibromochloromethane
4.702 µg/L
No EPA limit set
worst single sample: 8.38 µg/L
35/49 SYR4 2012–2019
Bromodichloromethane
5.657 µg/L
No EPA limit set
worst single sample: 10.5 µg/L
34/49 SYR4 2012–2019
TTHM
34.54 µg/L 43%
of the EPA limit 80 µg/L
worst single sample: 72.4 µg/L
32/49 SYR4 2012–2019
Chloroform
27.76 µg/L
No EPA limit set
worst single sample: 58.6 µg/L
29/49 SYR4 2012–2019
Bromoform
4.294 µg/L
No EPA limit set
worst single sample: 4.91 µg/L
27/49 SYR4 2012–2019
Monochloroacetic Acid
3.932 µg/L
No EPA limit set
worst single sample: 4.49 µg/L
19/49 SYR4 2012–2019
Lead
7.48 µg/L 50%
of the EPA limit 15 µg/L
worst single sample: 10 µg/L
15/90 SYR4 2013–2019
Lead
0.0056 mg/L 37%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Trichloroacetic Acid
2.964 µg/L
No EPA limit set
worst single sample: 3.21 µg/L
13/49 SYR4 2012–2019
Dibromoacetic Acid
1.363 µg/L
No EPA limit set
worst single sample: 1.55 µg/L
12/49 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
14.165 µg/L 24%
of the EPA limit 60 µg/L
worst single sample: 15.6 µg/L
8/49 SYR4 2012–2019
Dichloroacetic Acid
8.486 µg/L
No EPA limit set
worst single sample: 9.92 µg/L
7/49 SYR4 2012–2019
Lithium
250 µg/L
No EPA limit set
6/6 UCMR-5 2025
Barium
13.3 µg/L 0.7%
of the EPA limit 2000 µg/L
1/1 SYR4 2016
Fluoride
1600 µg/L 40%
of the EPA limit 4000 µg/L
1/1 SYR4 2016
Gross Alpha, Excl. Radon And U
18.2 pCi/L 121%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
1/1 SYR4 2019
71 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBenzeneBenzo(A)PyreneChlorobenzeneCadmiumCarbon TetrachlorideChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylbenzeneHfpo-DaLassoMercuryMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ALTOONA WATER SUPPLY
Phone
515-967-4464
Email
[email protected]

Frequently asked questions about Altoona Water Supply

Is Altoona Water Supply tap water safe to drink?

EPA monitoring detected 19 contaminants in Altoona Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Altoona Water Supply's water?

EPA monitoring detected Copper, Combined Radium (-226 And -228), Nitrate, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Altoona Water Supply serve?

Altoona Water Supply reports serving 19,565 people in Iowa, per its EPA record.

Has Altoona Water Supply had any water quality violations?

The EPA has 73 violations on file for Altoona Water Supply, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.