Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2002-09-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-09-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-09-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-09-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-09-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-08-01 → 2002-08-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 9600 µg/L 96% of the EPA limit 10000 µg/L
worst single sample: 10200 µg/L | 208/224 | SYR4 | 2012–2019 |
| Copper | 541.3 µg/L 42% of the EPA limit 1300 µg/L
worst single sample: 881 µg/L | 60/60 | SYR4 | 2012–2018 |
| Lead | 19.32 µg/L 129% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 227 µg/L | 37/60 | SYR4 | 2012–2018 |
| Lead | 0.0114 mg/L 76% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2024 |
| Dibromochloromethane | 4.426 µg/L No EPA limit set
worst single sample: 4.45 µg/L | 7/7 | SYR4 | 2013–2019 |
| Bromodichloromethane | 6.0375 µg/L No EPA limit set
worst single sample: 6.14 µg/L | 6/7 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.3025 µg/L No EPA limit set
worst single sample: 2.36 µg/L | 6/7 | SYR4 | 2013–2019 |
| TTHM | 18.425 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 18.6 µg/L | 6/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 15.25 µg/L 25% of the EPA limit 60 µg/L
worst single sample: 16.5 µg/L | 6/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.2625 µg/L No EPA limit set
worst single sample: 1.29 µg/L | 6/7 | SYR4 | 2013–2019 |
| Bromoform | 2.814 µg/L No EPA limit set
worst single sample: 2.93 µg/L | 5/7 | SYR4 | 2013–2019 |
| Chloroform | 7.452 µg/L No EPA limit set
worst single sample: 7.79 µg/L | 5/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 4.27 µg/L No EPA limit set
worst single sample: 4.33 µg/L | 5/7 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 8.156 µg/L No EPA limit set
worst single sample: 9.04 µg/L | 5/7 | SYR4 | 2013–2019 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Osage Municipal Water Supply
Is Osage Municipal Water Supply tap water safe to drink?
EPA monitoring detected 16 contaminants in Osage Municipal Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Osage Municipal Water Supply's water?
EPA monitoring detected Nitrate, Copper, Lead, Lead, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Osage Municipal Water Supply serve?
Osage Municipal Water Supply reports serving 3,637 people in Iowa, per its EPA record.
Has Osage Municipal Water Supply had any water quality violations?
The EPA has 57 violations on file for Osage Municipal Water Supply, of which 48 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.