Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1995-01-01 → 1995-01-31 |
| MCL | Health-based | Resolved | 1995-01-01 → 1995-01-31 |
| MCL | Health-based | Resolved | 1995-01-01 → 1995-01-31 |
| MCL | Health-based | Resolved | 1995-01-01 → 1995-01-31 |
| MR | Monitoring | Archived | 2025-04-01 → 2026-03-31 |
| MR | Monitoring | Resolved | 1992-12-01 → 1992-12-31 |
| MR | Monitoring | Resolved | 1992-12-01 → 1992-12-31 |
| MR | Monitoring | Resolved | 1992-12-01 → 1992-12-31 |
| MR | Monitoring | Resolved | 1992-12-01 → 1992-12-31 |
| MR | Monitoring | Resolved | 1992-12-01 → 1992-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1000 µg/L 10% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0140 mg/L 93% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2023 |
| Copper | 172 µg/L 13% of the EPA limit 1300 µg/L
worst single sample: 190 µg/L | 10/10 | SYR4 | 2014–2017 |
| Lead | 12.8 µg/L 85% of the EPA limit 15 µg/L
worst single sample: 13 µg/L | 3/10 | SYR4 | 2014–2017 |
| Bromodichloromethane | 13.9 µg/L No EPA limit set
worst single sample: 14 µg/L | 2/2 | SYR4 | 2013–2016 |
| Bromoform | 0.9900 µg/L No EPA limit set
worst single sample: 1 µg/L | 2/2 | SYR4 | 2013–2016 |
| Chloroform | 16.9 µg/L No EPA limit set
worst single sample: 17 µg/L | 2/2 | SYR4 | 2013–2016 |
| Dibromochloromethane | 7.43 µg/L No EPA limit set
worst single sample: 7.5 µg/L | 2/2 | SYR4 | 2013–2016 |
| TTHM | 38.75 µg/L 48% of the EPA limit 80 µg/L
worst single sample: 39 µg/L | 2/2 | SYR4 | 2013–2016 |
| Dichloroacetic Acid | 1 µg/L No EPA limit set | 1/2 | SYR4 | 2013–2016 |
| Fluoride | 100 µg/L 2.5% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2013 |
| Monobromoacetic Acid | 4 µg/L No EPA limit set | 1/2 | SYR4 | 2013–2016 |
| Total Haloacetic Acids (HAA5) | 10 µg/L 17% of the EPA limit 60 µg/L | 1/2 | SYR4 | 2013–2016 |
| Trichloroacetic Acid | 5 µg/L No EPA limit set | 1/2 | SYR4 | 2013–2016 |
46 contaminants tested, none detected
Utility contact
Frequently asked questions about Fenton Municipal Water Supply
Is Fenton Municipal Water Supply tap water safe to drink?
EPA monitoring detected 14 contaminants in Fenton Municipal Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fenton Municipal Water Supply's water?
EPA monitoring detected Nitrate, Lead, Copper, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Fenton Municipal Water Supply serve?
Fenton Municipal Water Supply reports serving 254 people in Iowa, per its EPA record.
Has Fenton Municipal Water Supply had any water quality violations?
The EPA has 13 violations on file for Fenton Municipal Water Supply, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.