Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-03-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| Other | Monitoring | Unaddressed | 2021-04-26 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 2280 µg/L 175% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 3490 µg/L | 71/71 | SYR4 | 2012–2019 |
| Lead | 9.5 µg/L 63% of the EPA limit 15 µg/L
worst single sample: 36.4 µg/L | 46/71 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2024 |
| Chloroform | 43.72 µg/L No EPA limit set
worst single sample: 44.2 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 15.34 µg/L No EPA limit set
worst single sample: 15.4 µg/L | 7/7 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 21.19 µg/L No EPA limit set
worst single sample: 21.7 µg/L | 7/7 | SYR4 | 2013–2019 |
| Nitrite | 1961 µg/L 196% of the EPA limit, at the 95th percentile of samples — 1000 µg/L
worst single sample: 2450 µg/L | 7/89 | SYR4 | 2013–2019 |
| TTHM | 48.65 µg/L 61% of the EPA limit 80 µg/L
worst single sample: 49.1 µg/L | 7/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 45 µg/L 75% of the EPA limit 60 µg/L
worst single sample: 45.9 µg/L | 7/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 19.69 µg/L No EPA limit set
worst single sample: 22.6 µg/L | 7/7 | SYR4 | 2013–2019 |
| Nitrate | 800 µg/L 8% of the EPA limit 10000 µg/L | 6/18 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.736 µg/L No EPA limit set
worst single sample: 4.85 µg/L | 5/7 | SYR4 | 2013–2019 |
| Dibromochloromethane | 2.224 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 2/7 | SYR4 | 2013–2019 |
| Arsenic | 8.5 µg/L 85% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2013–2019 |
| Barium | 623 µg/L 31% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2016 |
| Fluoride | 400 µg/L 10% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2016 |
45 contaminants tested, none detected
Utility contact
Frequently asked questions about Granger Muni Water Supply
Is Granger Muni Water Supply tap water safe to drink?
EPA monitoring detected 16 contaminants in Granger Muni Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Granger Muni Water Supply's water?
EPA monitoring detected Copper, Lead, Lead, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Granger Muni Water Supply serve?
Granger Muni Water Supply reports serving 1,654 people in Iowa, per its EPA record.
Has Granger Muni Water Supply had any water quality violations?
The EPA has 24 violations on file for Granger Muni Water Supply, of which 5 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.