← Iowa

Tap water quality report

Brookhill Estates

EPA monitoring tested this supplier for 48 contaminants and detected 6. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

48
contaminants tested
6
detected
41
people served
35
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Clinton

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

35
health-based violations
74
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2013-06-01 → 2013-06-30
MCL Health-based Resolved 2013-06-01 → 2013-06-30
MCL Health-based Resolved 2013-06-01 → 2013-06-30
MCL Health-based Resolved 2013-06-01 → 2013-06-30
MCL Health-based Resolved 2013-06-01 → 2013-06-30
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
9200 µg/L 92%
of the EPA limit 10000 µg/L
worst single sample: 9600 µg/L
62/64 SYR4 2012–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
12/12 LCR 2023
Copper
165.5 µg/L 13%
of the EPA limit 1300 µg/L
worst single sample: 170 µg/L
10/10 SYR4 2014–2017
Lead
4.54 µg/L 30%
of the EPA limit 15 µg/L
worst single sample: 4.9 µg/L
5/10 SYR4 2014–2017
Barium
86 µg/L 4.3%
of the EPA limit 2000 µg/L
1/1 SYR4 2014
Fluoride
192 µg/L 4.8%
of the EPA limit 4000 µg/L
1/1 SYR4 2014
42 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBenzeneBenzo(A)PyreneChlorobenzeneCadmiumCarbon TetrachlorideChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylbenzeneGlyphosateLassoMercuryPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BROOKHILL ESTATES HOA
Phone
563-289-3373
Email
[email protected]

Frequently asked questions about Brookhill Estates

Is Brookhill Estates tap water safe to drink?

EPA monitoring detected 6 contaminants in Brookhill Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Brookhill Estates's water?

EPA monitoring detected Nitrate, Lead, Copper, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Brookhill Estates serve?

Brookhill Estates reports serving 41 people in Iowa, per its EPA record.

Has Brookhill Estates had any water quality violations?

The EPA has 74 violations on file for Brookhill Estates, of which 35 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.