← Hawaii

Tap water quality report

Haena-Wainiha

EPA monitoring tested this supplier for 84 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

84
contaminants tested
10
detected
833
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Kauai

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
4
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2013-01-01 → 2013-01-31
MR Monitoring Resolved 2013-01-01 → 2013-01-31
MR Monitoring Resolved 2013-01-01 → 2013-01-31
MR Monitoring Archived 2000-01-01 → 2003-12-08

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1212.8 µg/L 93%
of the EPA limit 1300 µg/L
worst single sample: 1717 µg/L
57/77 SYR4 2014–2019
Nitrate
470 µg/L 4.7%
of the EPA limit 10000 µg/L
20/42 SYR4 2012–2019
Lead
4.614 µg/L 31%
of the EPA limit 15 µg/L
worst single sample: 6.09 µg/L
9/76 SYR4 2014–2019
Nitrate-Nitrite
466 µg/L 4.7%
of the EPA limit 10000 µg/L
worst single sample: 470 µg/L
9/20 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
6/6 LCR 2023
Chromium
7.58 µg/L 7.6%
of the EPA limit 100 µg/L
worst single sample: 7.73 µg/L
2/5 SYR4 2016–2018
TTHM
3.215 µg/L 4%
of the EPA limit 80 µg/L
worst single sample: 3.3 µg/L
2/9 SYR4 2012–2019
Bromodichloromethane
0.7400 µg/L
No EPA limit set
1/9 SYR4 2012–2019
Bromoform
1.6 µg/L
No EPA limit set
1/9 SYR4 2012–2019
Chloroform
2.6 µg/L
No EPA limit set
1/9 SYR4 2012–2019
74 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KNOFF, MARK
Phone
808-245-5403
Email
[email protected]

Frequently asked questions about Haena-Wainiha

Is Haena-Wainiha tap water safe to drink?

EPA monitoring detected 10 contaminants in Haena-Wainiha's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Haena-Wainiha's water?

EPA monitoring detected Copper, Nitrate, Lead, Nitrate-Nitrite, Lead, and others. The full list with the level and data source for each is above.

How many people does Haena-Wainiha serve?

Haena-Wainiha reports serving 833 people in Hawaii, per its EPA record.

Has Haena-Wainiha had any water quality violations?

The EPA has 4 violations on file for Haena-Wainiha, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.