← Florida

Tap water quality report

Winter Haven Water Department

EPA monitoring tested this supplier for 99 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

99
contaminants tested
12
detected
87,537
people served
10
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Polk

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

10
health-based violations
44
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Resolved 2021-09-01 → 2021-09-30
MCL Health-based Archived 1995-07-01 → 1995-07-31
MCL Health-based Resolved 1994-07-01 → 1994-07-31
MCL Health-based Resolved 1994-07-01 → 1994-07-31
MCL Health-based Resolved 1994-07-01 → 1994-07-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOS 0.0060 µg/L 4/18 2024
PFHXS 0.0045 µg/L 3/18 2024
PFBS 0.0049 µg/L 2/18 2024
PFOA 0.0059 µg/L 2/18 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
81.64 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 136 µg/L
177/177 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
72.56 µg/L 121%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 153 µg/L
177/177 SYR4 2012–2019
Fluoride
1050 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1300 µg/L
60/64 SYR4 2012–2017
Nitrate
849.25 µg/L 8.5%
of the EPA limit 10000 µg/L
worst single sample: 976 µg/L
26/156 SYR4 2012–2019
Barium
18.5 µg/L 0.9%
of the EPA limit 2000 µg/L
17/17 SYR4 2014–2017
Lead
0.0070 mg/L 47%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Copper
3.005 µg/L 0.2%
of the EPA limit 1300 µg/L
worst single sample: 3.2 µg/L
4/17 SYR4 2014–2017
Arsenic
3.53 µg/L 35%
of the EPA limit 10 µg/L
worst single sample: 3.6 µg/L
2/17 SYR4 2014–2017
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WINTER HAVEN, CITY OF
Phone
863-291-5851

Frequently asked questions about Winter Haven Water Department

Is Winter Haven Water Department tap water safe to drink?

EPA monitoring detected 12 contaminants in Winter Haven Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Winter Haven Water Department's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Fluoride, Nitrate, Barium, and others. The full list with the level and data source for each is above.

How many people does Winter Haven Water Department serve?

Winter Haven Water Department reports serving 87,537 people in Florida, per its EPA record.

Has Winter Haven Water Department had any water quality violations?

The EPA has 44 violations on file for Winter Haven Water Department, of which 10 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.