← Florida

Tap water quality report

Belleair Water Plant

EPA monitoring tested this supplier for 98 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
17
detected
5,299
people served
50
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Pinellas

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

50
health-based violations
83
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2022-10-01 → 2022-12-31
MCL Health-based Archived 2022-07-01 → 2022-09-30
MCL Health-based Archived 2022-04-01 → 2022-06-30
MCL Health-based Archived 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfpea 0.0046 µg/L 3/3 2025
PFBS 0.0048 µg/L 2/3 2025
Pfhxa 0.0039 µg/L 2/3 2025
PFOA 0.0053 µg/L 1/3 2025
PFOS 0.0090 µg/L 1/3 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
803.5 µg/L 8%
of the EPA limit 10000 µg/L
worst single sample: 870 µg/L
28/32 SYR4 2012–2019
Lead
0.0018 mg/L 12%
of the EPA limit 0.0150 mg/L
16/16 LCR 2024
TTHM
79.42 µg/L 99%
of the EPA limit 80 µg/L
worst single sample: 82.5 µg/L
15/15 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
17.166 µg/L 29%
of the EPA limit 60 µg/L
worst single sample: 18.31 µg/L
14/14 SYR4 2012–2019
Fluoride
670 µg/L 17%
of the EPA limit 4000 µg/L
7/7 SYR4 2014–2017
cis-1,2-Dichloroethylene
0.4000 µg/L 0.6%
of the EPA limit 70 µg/L
5/8 SYR4 2012–2018
Arsenic
6.28 µg/L 63%
of the EPA limit 10 µg/L
worst single sample: 6.7 µg/L
3/3 SYR4 2014–2017
Barium
20.64 µg/L 1%
of the EPA limit 2000 µg/L
worst single sample: 20.7 µg/L
3/3 SYR4 2014–2017
Copper
4.74 µg/L 0.4%
of the EPA limit 1300 µg/L
worst single sample: 4.8 µg/L
3/3 SYR4 2014–2017
Nitrite
174.5 µg/L 17%
of the EPA limit 1000 µg/L
worst single sample: 180 µg/L
2/17 SYR4 2012–2019
Chromium
7.6 µg/L 7.6%
of the EPA limit 100 µg/L
1/4 SYR4 2014–2017
Selenium
9.3 µg/L 19%
of the EPA limit 50 µg/L
1/4 SYR4 2014–2017
81 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, TotalLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TOWN OF BELLEAIR
Phone
727-588-3795

Frequently asked questions about Belleair Water Plant

Is Belleair Water Plant tap water safe to drink?

EPA monitoring detected 17 contaminants in Belleair Water Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Belleair Water Plant's water?

EPA monitoring detected Nitrate, Lead, TTHM, Total Haloacetic Acids (HAA5), Fluoride, and others. The full list with the level and data source for each is above.

How many people does Belleair Water Plant serve?

Belleair Water Plant reports serving 5,299 people in Florida, per its EPA record.

Has Belleair Water Plant had any water quality violations?

The EPA has 83 violations on file for Belleair Water Plant, of which 50 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.