← Florida

Tap water quality report

Zephyrhills City of

EPA monitoring tested this supplier for 99 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

99
contaminants tested
24
detected
29,117
people served
14
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Pasco

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
49
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Resolved 2015-10-01 → 2015-10-31
MCL Health-based Archived 2004-10-01 → 2004-10-31
MCL Health-based Archived 2001-06-01 → 2001-06-30
MCL Health-based Archived 2001-06-01 → 2001-06-30
MCL Health-based Archived 1999-12-01 → 1999-12-31
MCL Health-based Archived 1996-12-01 → 1996-12-31
MCL Health-based Archived 1996-06-01 → 1996-06-30
MCL Health-based Archived 1995-01-01 → 1995-01-31
MCL Health-based Archived 1994-10-01 → 1994-10-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0105 µg/L 7/14 2024
PFOS 0.0260 µg/L 7/14 2024
PFHXS 0.0181 µg/L 6/14 2024
Pfpea 0.0191 µg/L 4/14 2024
Pfhxa 0.0088 µg/L 3/14 2024
PFOA 0.0074 µg/L 3/14 2024
Pfhpa 0.0030 µg/L 2/14 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3700 µg/L 37%
of the EPA limit 10000 µg/L
worst single sample: 3900 µg/L
152/152 SYR4 2012–2019
TTHM
15.1045 µg/L 19%
of the EPA limit 80 µg/L
worst single sample: 22.85 µg/L
32/33 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
5.611 µg/L 9.4%
of the EPA limit 60 µg/L
worst single sample: 8.05 µg/L
19/33 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Barium
7.175 µg/L 0.4%
of the EPA limit 2000 µg/L
worst single sample: 11 µg/L
16/16 SYR4 2014–2017
Copper
6.605 µg/L 0.5%
of the EPA limit 1300 µg/L
worst single sample: 9.4 µg/L
14/16 SYR4 2014–2017
Arsenic
0.8450 µg/L 8.5%
of the EPA limit 10 µg/L
worst single sample: 0.9000 µg/L
12/16 SYR4 2014–2017
Fluoride
170 µg/L 4.3%
of the EPA limit 4000 µg/L
9/32 SYR4 2014–2017
Chromium
1.365 µg/L 1.4%
of the EPA limit 100 µg/L
worst single sample: 1.4 µg/L
8/16 SYR4 2014–2017
Cadmium
0.4750 µg/L 9.5%
of the EPA limit 5 µg/L
worst single sample: 0.5000 µg/L
6/16 SYR4 2014–2017
Selenium
1.58 µg/L 3.2%
of the EPA limit 50 µg/L
worst single sample: 1.7 µg/L
5/16 SYR4 2014–2017
Antimony, Total
0.6850 µg/L 11%
of the EPA limit 6 µg/L
worst single sample: 0.7000 µg/L
4/16 SYR4 2014–2017
Combined Uranium
1.19796 µg/L 4%
of the EPA limit 30 µg/L
4/4 SYR4 2017
Mercury
0.4850 µg/L 24%
of the EPA limit 2 µg/L
worst single sample: 0.5000 µg/L
4/16 SYR4 2014–2017
Thallium, Total
0.5850 µg/L 29%
of the EPA limit 2 µg/L
worst single sample: 0.6000 µg/L
4/16 SYR4 2014–2017
Lead
1.83 µg/L 12%
of the EPA limit 15 µg/L
worst single sample: 1.9 µg/L
3/16 SYR4 2014–2017
Nitrite
180 µg/L 18%
of the EPA limit 1000 µg/L
3/76 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPfdaPfdoaPfeesaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CITY OF ZEPHYRHILLS
Phone
813-780-0008

Frequently asked questions about Zephyrhills City of

Is Zephyrhills City of tap water safe to drink?

EPA monitoring detected 24 contaminants in Zephyrhills City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Zephyrhills City of's water?

EPA monitoring detected Nitrate, TTHM, Total Haloacetic Acids (HAA5), Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Zephyrhills City of serve?

Zephyrhills City of reports serving 29,117 people in Florida, per its EPA record.

Has Zephyrhills City of had any water quality violations?

The EPA has 49 violations on file for Zephyrhills City of, of which 14 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.