Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-02-01 |
| MON | Monitoring | Archived | 2025-06-01 → 2025-06-30 |
| MR | Monitoring | Archived | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Archived | 2006-07-01 → 2006-09-30 |
| MR | Monitoring | Archived | 2003-03-01 → 2003-03-31 |
| MR | Monitoring | Archived | 2003-01-01 → 2003-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 590 µg/L 5.9% of the EPA limit 10000 µg/L
worst single sample: 2720 µg/L | 122/124 | SYR4 | 2012–2019 |
| Fluoride | 513 µg/L 13% of the EPA limit 4000 µg/L
worst single sample: 530 µg/L | 38/38 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 18.8435 µg/L 31% of the EPA limit 60 µg/L
worst single sample: 30 µg/L | 38/38 | SYR4 | 2012–2019 |
| TTHM | 21.792 µg/L 27% of the EPA limit 80 µg/L
worst single sample: 24.6 µg/L | 37/38 | SYR4 | 2012–2019 |
| Barium | 19.3 µg/L 1% of the EPA limit 2000 µg/L
worst single sample: 21 µg/L | 18/18 | SYR4 | 2012–2019 |
| Copper | 22.3 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 23 µg/L | 15/64 | SYR4 | 2012–2019 |
| Combined Uranium | 3.04705 µg/L 10% of the EPA limit 30 µg/L
worst single sample: 3.129 µg/L | 12/19 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 5.28 pCi/L 35% of the EPA limit 15 pCi/L
worst single sample: 6.3 pCi/L | 7/15 | SYR4 | 2012–2017 |
| Antimony, Total | 2.06 µg/L 34% of the EPA limit 6 µg/L
worst single sample: 2.2 µg/L | 5/18 | SYR4 | 2012–2019 |
| Arsenic | 0.6800 µg/L 6.8% of the EPA limit 10 µg/L
worst single sample: 0.7000 µg/L | 5/18 | SYR4 | 2012–2019 |
| Lead | 2.72 µg/L 18% of the EPA limit 15 µg/L
worst single sample: 3 µg/L | 3/65 | SYR4 | 2012–2019 |
| Selenium | 9.1 µg/L 18% of the EPA limit 50 µg/L
worst single sample: 10 µg/L | 3/20 | SYR4 | 2012–2019 |
| Thallium, Total | 0.3900 µg/L 20% of the EPA limit 2 µg/L
worst single sample: 0.4000 µg/L | 2/19 | SYR4 | 2012–2019 |
| Cyanide | 10 µg/L 5% of the EPA limit 200 µg/L | 1/19 | SYR4 | 2012–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Tampa Bay Water Reg. Surface Water Plant
Is Tampa Bay Water Reg. Surface Water Plant tap water safe to drink?
EPA monitoring detected 14 contaminants in Tampa Bay Water Reg. Surface Water Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Tampa Bay Water Reg. Surface Water Plant's water?
EPA monitoring detected Nitrate, Fluoride, Total Haloacetic Acids (HAA5), TTHM, Barium, and others. The full list with the level and data source for each is above.
How many people does Tampa Bay Water Reg. Surface Water Plant serve?
Tampa Bay Water Reg. Surface Water Plant reports serving 25 people in Florida, per its EPA record.
Has Tampa Bay Water Reg. Surface Water Plant had any water quality violations?
The EPA has 6 violations on file for Tampa Bay Water Reg. Surface Water Plant, of which 1 is health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.