← Florida

Tap water quality report

Leisure Lakes (Covered Bridge)

EPA monitoring tested this supplier for 69 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

69
contaminants tested
11
detected
632
people served
25
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Highlands

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

25
health-based violations
34
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2013-07-01 → 2013-09-30
MCL Health-based Resolved 2013-07-01 → 2013-09-30
MCL Health-based Resolved 2013-07-01 → 2013-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
114.5 µg/L 143%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 143 µg/L
31/31 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
89.88 µg/L 150%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 129.78 µg/L
31/31 SYR4 2012–2019
Lead
0.0100 mg/L 67%
of the EPA limit 0.0150 mg/L
21/21 LCR 2024
Nitrate
130 µg/L 1.3%
of the EPA limit 10000 µg/L
10/18 SYR4 2012–2019
Fluoride
280 µg/L 7%
of the EPA limit 4000 µg/L
4/6 SYR4 2012–2018
Barium
126.3 µg/L 6.3%
of the EPA limit 2000 µg/L
worst single sample: 127 µg/L
3/3 SYR4 2012–2018
Copper
11 µg/L 0.8%
of the EPA limit 1300 µg/L
2/3 SYR4 2012–2018
Dalapon
0.8300 µg/L 0.4%
of the EPA limit 200 µg/L
worst single sample: 0.8500 µg/L
2/3 SYR4 2012–2018
Arsenic
1.1 µg/L 11%
of the EPA limit 10 µg/L
1/3 SYR4 2012–2018
Lead
1 µg/L 6.7%
of the EPA limit 15 µg/L
1/3 SYR4 2012–2018
Nitrite
100 µg/L 10%
of the EPA limit 1000 µg/L
1/9 SYR4 2012–2019
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GARY A DEREMER
Phone
727-848-8292

Frequently asked questions about Leisure Lakes (Covered Bridge)

Is Leisure Lakes (Covered Bridge) tap water safe to drink?

EPA monitoring detected 11 contaminants in Leisure Lakes (Covered Bridge)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Leisure Lakes (Covered Bridge)'s water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Leisure Lakes (Covered Bridge) serve?

Leisure Lakes (Covered Bridge) reports serving 632 people in Florida, per its EPA record.

Has Leisure Lakes (Covered Bridge) had any water quality violations?

The EPA has 34 violations on file for Leisure Lakes (Covered Bridge), of which 25 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.