← Florida

Tap water quality report

Inverness Water Dept

EPA monitoring tested this supplier for 98 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
18
detected
7,194
people served
32
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Citrus

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

32
health-based violations
59
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-07-01 → 2014-07-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-07-01 → 2010-09-30
MCL Health-based Archived 2010-07-01 → 2010-09-30
MCL Health-based Archived 2010-07-01 → 2010-09-30
MCL Health-based Archived 2010-04-01 → 2010-06-30
MCL Health-based Archived 2010-01-01 → 2010-03-31
MCL Health-based Archived 2010-01-01 → 2010-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0035 µg/L 2/2 2025
PFHXS 0.0060 µg/L 2/2 2025
PFOS 0.0091 µg/L 2/2 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
1375 µg/L 34%
of the EPA limit 4000 µg/L
worst single sample: 1500 µg/L
126/128 SYR4 2012–2019
TTHM
76.961 µg/L 96%
of the EPA limit 80 µg/L
worst single sample: 130.87 µg/L
67/67 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
37.463 µg/L 62%
of the EPA limit 60 µg/L
worst single sample: 70.89 µg/L
63/66 SYR4 2012–2019
Nitrate
3580 µg/L 36%
of the EPA limit 10000 µg/L
worst single sample: 4300 µg/L
30/50 SYR4 2012–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Nitrite
315 µg/L 32%
of the EPA limit 1000 µg/L
worst single sample: 320 µg/L
6/28 SYR4 2012–2019
Barium
5.02 µg/L 0.3%
of the EPA limit 2000 µg/L
worst single sample: 5.1 µg/L
3/3 SYR4 2014–2017
Copper
7.39 µg/L 0.6%
of the EPA limit 1300 µg/L
worst single sample: 7.6 µg/L
3/3 SYR4 2014–2017
Arsenic
0.2950 µg/L 2.9%
of the EPA limit 10 µg/L
worst single sample: 0.3000 µg/L
2/3 SYR4 2014–2017
Antimony, Total
0.3000 µg/L 5%
of the EPA limit 6 µg/L
1/3 SYR4 2014–2017
Beryllium, Total
0.1000 µg/L 2.5%
of the EPA limit 4 µg/L
1/3 SYR4 2014–2017
Chromium
3.3 µg/L 3.3%
of the EPA limit 100 µg/L
1/3 SYR4 2014–2017
Dichloromethane
1.5 µg/L 30%
of the EPA limit 5 µg/L
1/4 SYR4 2014–2017
Lead
0.2000 µg/L 1.3%
of the EPA limit 15 µg/L
1/3 SYR4 2014–2017
Selenium
0.8000 µg/L 1.6%
of the EPA limit 50 µg/L
1/3 SYR4 2014–2017
80 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ERIC WILLIAMS
Phone
352-726-2611

Frequently asked questions about Inverness Water Dept

Is Inverness Water Dept tap water safe to drink?

EPA monitoring detected 18 contaminants in Inverness Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Inverness Water Dept's water?

EPA monitoring detected Fluoride, TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, and others. The full list with the level and data source for each is above.

How many people does Inverness Water Dept serve?

Inverness Water Dept reports serving 7,194 people in Florida, per its EPA record.

Has Inverness Water Dept had any water quality violations?

The EPA has 59 violations on file for Inverness Water Dept, of which 32 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.