← Florida

Tap water quality report

Little Gasparilla Water Utility Inc

EPA monitoring tested this supplier for 68 contaminants and detected 5. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

68
contaminants tested
5
detected
1,330
people served
1
health-based violations
Water source
SWP
Ownership
Private
Counties served
Charlotte

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
43
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2011-06-01 → 2011-06-30
MR Monitoring Resolved 2024-01-01
RPT Monitoring Unaddressed 2023-11-01
MR Monitoring Unaddressed 2022-07-01
MR Monitoring Resolved 2021-04-01 → 2021-06-30
MR Monitoring Resolved 2021-04-01 → 2021-06-30
MR Monitoring Resolved 2021-04-01 → 2021-06-30
MR Monitoring Resolved 2021-04-01 → 2021-06-30
MR Monitoring Resolved 2021-04-01 → 2021-06-30
MR Monitoring Resolved 2021-04-01 → 2021-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.00020 mg/L 1.3%
of the EPA limit 0.0150 mg/L
18/18 LCR 2023
TTHM
41.7 µg/L 52%
of the EPA limit 80 µg/L
worst single sample: 42 µg/L
7/7 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
31.275 µg/L 52%
of the EPA limit 60 µg/L
worst single sample: 34 µg/L
6/7 SYR4 2012–2019
Mercury
0.1000 µg/L 5%
of the EPA limit 2 µg/L
1/1 SYR4 2012
Nitrite
20 µg/L 2%
of the EPA limit 1000 µg/L
1/3 SYR4 2012–2014
63 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMethoxychlorNitrateOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JACK BOYER
Phone
941-681-2778

Frequently asked questions about Little Gasparilla Water Utility Inc

Is Little Gasparilla Water Utility Inc tap water safe to drink?

EPA monitoring detected 5 contaminants in Little Gasparilla Water Utility Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Little Gasparilla Water Utility Inc's water?

EPA monitoring detected Lead, TTHM, Total Haloacetic Acids (HAA5), Mercury, Nitrite. The full list with the level and data source for each is above.

How many people does Little Gasparilla Water Utility Inc serve?

Little Gasparilla Water Utility Inc reports serving 1,330 people in Florida, per its EPA record.

Has Little Gasparilla Water Utility Inc had any water quality violations?

The EPA has 43 violations on file for Little Gasparilla Water Utility Inc, of which 1 is health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.