Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| Other | Monitoring | Resolved | 2024-07-01 |
| MON | Monitoring | Resolved | 2024-01-01 → 2024-01-31 |
| MR | Monitoring | Resolved | 2022-07-01 → 2022-09-30 |
| MR | Monitoring | Resolved | 2022-07-01 → 2022-09-30 |
| MR | Monitoring | Resolved | 2022-07-01 → 2022-09-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 78.745 µg/L 98% of the EPA limit 80 µg/L
worst single sample: 126.46 µg/L | 128/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 56.3845 µg/L 94% of the EPA limit 60 µg/L
worst single sample: 91.34 µg/L | 128/128 | SYR4 | 2012–2019 |
| Arsenic | 3.46 µg/L 35% of the EPA limit 10 µg/L
worst single sample: 4.1 µg/L | 29/54 | SYR4 | 2012–2019 |
| Nitrate | 431.75 µg/L 4.3% of the EPA limit 10000 µg/L
worst single sample: 435 µg/L | 22/24 | SYR4 | 2012–2019 |
| Lead | 0.0044 mg/L 29% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2023 |
| Barium | 33.65 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 34 µg/L | 8/8 | SYR4 | 2012–2019 |
| Nitrite | 27.5 µg/L 2.8% of the EPA limit 1000 µg/L
worst single sample: 30 µg/L | 6/12 | SYR4 | 2012–2019 |
| Copper | 1.625 µg/L 0.1% of the EPA limit 1300 µg/L
worst single sample: 1.7 µg/L | 4/4 | SYR4 | 2012–2017 |
| Cyanide | 46.6 µg/L 23% of the EPA limit 200 µg/L
worst single sample: 48 µg/L | 3/9 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 5.248 pCi/L 35% of the EPA limit 15 pCi/L
worst single sample: 5.51 pCi/L | 3/4 | SYR4 | 2014–2017 |
| Antimony, Total | 0.4950 µg/L 8.3% of the EPA limit 6 µg/L
worst single sample: 0.5000 µg/L | 2/8 | SYR4 | 2012–2019 |
| Fluoride | 119 µg/L 3% of the EPA limit 4000 µg/L
worst single sample: 120 µg/L | 2/12 | SYR4 | 2012–2019 |
| Combined Uranium | 0.0939 µg/L 0.3% of the EPA limit 30 µg/L | 1/10 | SYR4 | 2012–2017 |
| Dalapon | 1.5 µg/L 0.8% of the EPA limit 200 µg/L | 1/9 | SYR4 | 2012–2019 |
| Diquat | 0.3600 µg/L 1.8% of the EPA limit 20 µg/L | 1/6 | SYR4 | 2012–2017 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Punta Gorda
Is City of Punta Gorda tap water safe to drink?
EPA monitoring detected 19 contaminants in City of Punta Gorda's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Punta Gorda's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Arsenic, Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does City of Punta Gorda serve?
City of Punta Gorda reports serving 36,302 people in Florida, per its EPA record.
Has City of Punta Gorda had any water quality violations?
The EPA has 14 violations on file for City of Punta Gorda, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.