Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Unaddressed | 2025-07-01 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| Other | Monitoring | Resolved | 2024-07-01 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2024 |
| TTHM | 55.61 µg/L 70% of the EPA limit 80 µg/L
worst single sample: 55.7 µg/L | 10/10 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 21.1665 µg/L 35% of the EPA limit 60 µg/L
worst single sample: 24.33 µg/L | 10/10 | SYR4 | 2012–2018 |
| Nitrate | 70 µg/L 0.7% of the EPA limit 10000 µg/L | 8/16 | SYR4 | 2012–2019 |
| Xylenes, Total | 1.96 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 2.1 µg/L | 5/10 | SYR4 | 2012–2019 |
| Fluoride | 420 µg/L 11% of the EPA limit 4000 µg/L | 4/6 | SYR4 | 2012–2018 |
| Barium | 22.9 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 23 µg/L | 3/3 | SYR4 | 2012–2018 |
| Dalapon | 0.8835 µg/L 0.4% of the EPA limit 200 µg/L
worst single sample: 0.9000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Ethylbenzene | 0.2950 µg/L 0% of the EPA limit 700 µg/L
worst single sample: 0.3000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Selenium | 1.855 µg/L 3.7% of the EPA limit 50 µg/L
worst single sample: 1.9 µg/L | 2/3 | SYR4 | 2012–2018 |
| Arsenic | 1.5 µg/L 15% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2012–2018 |
| Copper | 2 µg/L 0.2% of the EPA limit 1300 µg/L | 1/3 | SYR4 | 2012–2018 |
| Chromium | 0.5000 µg/L 0.5% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2018 |
| Hexachlorocyclopentadiene | 0.0140 µg/L 0% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2012–2018 |
54 contaminants tested, none detected
Utility contact
Frequently asked questions about Highway Park Wtp
Is Highway Park Wtp tap water safe to drink?
EPA monitoring detected 14 contaminants in Highway Park Wtp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Highway Park Wtp's water?
EPA monitoring detected Lead, TTHM, Total Haloacetic Acids (HAA5), Nitrate, Xylenes, Total, and others. The full list with the level and data source for each is above.
How many people does Highway Park Wtp serve?
Highway Park Wtp reports serving 1,168 people in Florida, per its EPA record.
Has Highway Park Wtp had any water quality violations?
The EPA has 15 violations on file for Highway Park Wtp, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.