← Florida

Tap water quality report

Immokalee Water

EPA monitoring tested this supplier for 100 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
16
detected
26,841
people served
36
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Collier

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

36
health-based violations
93
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2012-07-01 → 2012-07-31
MCL Health-based Archived 2011-10-01 → 2011-10-31
MCL Health-based Archived 2008-09-01 → 2008-09-30
MCL Health-based Archived 2008-09-01 → 2008-09-30
MCL Health-based Archived 2008-05-01 → 2008-05-31
MCL Health-based Archived 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOS 0.0121 µg/L 6/6 2023
PFHXS 0.0044 µg/L 4/6 2023
PFOA 0.0042 µg/L 1/6 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
41.4285 µg/L 52%
of the EPA limit 80 µg/L
worst single sample: 61.6 µg/L
48/48 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
67.9705 µg/L 113%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 77.57 µg/L
48/48 SYR4 2012–2019
Nitrate
187 µg/L 1.9%
of the EPA limit 10000 µg/L
20/48 SYR4 2012–2019
Lead
0.00090 mg/L 6%
of the EPA limit 0.0150 mg/L
17/17 LCR 2023
Fluoride
841.85 µg/L 21%
of the EPA limit 4000 µg/L
worst single sample: 893 µg/L
12/12 SYR4 2014–2017
1,2-Dichloropropane
1.855 µg/L 37%
of the EPA limit 5 µg/L
worst single sample: 1.94 µg/L
6/13 SYR4 2012–2019
Barium
20.625 µg/L 1%
of the EPA limit 2000 µg/L
worst single sample: 22.3 µg/L
6/6 SYR4 2014–2017
Copper
29.34 µg/L 2.3%
of the EPA limit 1300 µg/L
worst single sample: 36 µg/L
5/6 SYR4 2014–2017
Arsenic
5.75 µg/L 57%
of the EPA limit 10 µg/L
worst single sample: 6.2 µg/L
3/6 SYR4 2014–2017
Cyanide
8.6 µg/L 4.3%
of the EPA limit 200 µg/L
1/7 SYR4 2014–2017
Dalapon
4.6 µg/L 2.3%
of the EPA limit 200 µg/L
1/20 SYR4 2014–2019
Lead
2.9 µg/L 19%
of the EPA limit 15 µg/L
1/6 SYR4 2014–2017
Nitrite
10 µg/L 1%
of the EPA limit 1000 µg/L
1/24 SYR4 2012–2019
84 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SARAH CATALA
Phone
239-658-3630

Frequently asked questions about Immokalee Water

Is Immokalee Water tap water safe to drink?

EPA monitoring detected 16 contaminants in Immokalee Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Immokalee Water's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Immokalee Water serve?

Immokalee Water reports serving 26,841 people in Florida, per its EPA record.

Has Immokalee Water had any water quality violations?

The EPA has 93 violations on file for Immokalee Water, of which 36 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.