Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2024-09-01 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2021-10-01 → 2021-10-31 |
| MR | Monitoring | Resolved | 2021-10-01 → 2021-10-31 |
| MR | Monitoring | Resolved | 2021-10-01 → 2021-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 94.8 µg/L 119% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 110 µg/L | 9/9 | SYR4 | 2017–2019 |
| Total Haloacetic Acids (HAA5) | 19 µg/L 32% of the EPA limit 60 µg/L
worst single sample: 21 µg/L | 9/9 | SYR4 | 2017–2019 |
| Lead | 0.00040 mg/L 2.7% of the EPA limit 0.0150 mg/L | 5/5 | LCR | 2022 |
| Fluoride | 585 µg/L 15% of the EPA limit 4000 µg/L
worst single sample: 600 µg/L | 4/4 | SYR4 | 2017–2018 |
| Barium | 9.3 µg/L 0.5% of the EPA limit 2000 µg/L | 1/2 | SYR4 | 2017–2018 |
| Copper | 6.9 µg/L 0.5% of the EPA limit 1300 µg/L | 1/2 | SYR4 | 2017–2018 |
| Di(2-ethylhexyl) Phthalate | 9.3 µg/L 155% of the EPA limit, at the 95th percentile of samples — 6 µg/L | 1/8 | SYR4 | 2017–2019 |
| Gross Alpha, Excl. Radon And U | 3.36 pCi/L 22% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Town and Country Utility
Is Town and Country Utility tap water safe to drink?
EPA monitoring detected 8 contaminants in Town and Country Utility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Town and Country Utility's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Fluoride, Barium, and others. The full list with the level and data source for each is above.
How many people does Town and Country Utility serve?
Town and Country Utility reports serving 13,427 people in Florida, per its EPA record.
Has Town and Country Utility had any water quality violations?
The EPA has 6 violations on file for Town and Country Utility, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.