← Florida

Tap water quality report

Boynton Beach

EPA monitoring tested this supplier for 100 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
17
detected
112,000
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Palm Beach

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
58
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 1998-08-01 → 1998-08-31
MCL Health-based Resolved 1998-08-01 → 1998-08-31
MCL Health-based Archived 1998-08-01 → 1998-08-31
MCL Health-based Resolved 1998-07-01 → 1998-07-31
MCL Health-based Resolved 1998-07-01 → 1998-07-31
MCL Health-based Archived 1998-07-01 → 1998-07-31
MCL Health-based Archived 1998-05-01 → 1998-05-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0064 µg/L 3/4 2024
Pfhxa 0.0056 µg/L 3/4 2024
Pfpea 0.0081 µg/L 3/4 2024
PFBS 0.0081 µg/L 2/4 2024
PFHXS 0.0070 µg/L 2/4 2024
PFOA 0.0087 µg/L 2/4 2024
PFOS 0.0260 µg/L 2/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
87.1 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 149 µg/L
177/178 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
38.605 µg/L 64%
of the EPA limit 60 µg/L
worst single sample: 52.7 µg/L
174/179 SYR4 2012–2019
Lead
0.0044 mg/L 29%
of the EPA limit 0.0150 mg/L
36/36 LCR 2025
Nitrate
474 µg/L 4.7%
of the EPA limit 10000 µg/L
worst single sample: 510 µg/L
30/32 SYR4 2012–2019
Fluoride
1100 µg/L 28%
of the EPA limit 4000 µg/L
8/8 SYR4 2014–2017
Barium
8.725 µg/L 0.4%
of the EPA limit 2000 µg/L
worst single sample: 8.8 µg/L
4/4 SYR4 2014–2017
Dalapon
2.76 µg/L 1.4%
of the EPA limit 200 µg/L
worst single sample: 2.8 µg/L
3/23 SYR4 2012–2019
Nitrite
30.4 µg/L 3%
of the EPA limit 1000 µg/L
worst single sample: 31 µg/L
3/16 SYR4 2012–2019
Arsenic
0.7900 µg/L 7.9%
of the EPA limit 10 µg/L
worst single sample: 0.8000 µg/L
2/4 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
0.4800 µg/L 8%
of the EPA limit 6 µg/L
1/9 SYR4 2012–2017
83 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CITY OF BOYNTON BEACH UTILITIES
Phone
561-742-6403

Frequently asked questions about Boynton Beach

Is Boynton Beach tap water safe to drink?

EPA monitoring detected 17 contaminants in Boynton Beach's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Boynton Beach's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Boynton Beach serve?

Boynton Beach reports serving 112,000 people in Florida, per its EPA record.

Has Boynton Beach had any water quality violations?

The EPA has 58 violations on file for Boynton Beach, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.