← Florida

Tap water quality report

Martin Co Utilities

EPA monitoring tested this supplier for 100 contaminants and detected 9. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
9
detected
104,105
people served
11
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Martin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

11
health-based violations
54
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01
TT Health-based Resolved 1992-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
62.65 µg/L 78%
of the EPA limit 80 µg/L
worst single sample: 71.7 µg/L
131/131 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
51.2 µg/L 85%
of the EPA limit 60 µg/L
worst single sample: 59.1 µg/L
131/131 SYR4 2012–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
27/27 LCR 2023
Nitrate
117.05 µg/L 1.2%
of the EPA limit 10000 µg/L
worst single sample: 120 µg/L
22/40 SYR4 2012–2019
Fluoride
520 µg/L 13%
of the EPA limit 4000 µg/L
16/16 SYR4 2014–2017
Barium
3.575 µg/L 0.2%
of the EPA limit 2000 µg/L
worst single sample: 3.7 µg/L
6/8 SYR4 2014–2017
Copper
154.25 µg/L 12%
of the EPA limit 1300 µg/L
worst single sample: 200 µg/L
6/10 SYR4 2014–2019
Nitrite
180.4 µg/L 18%
of the EPA limit 1000 µg/L
worst single sample: 220 µg/L
5/20 SYR4 2012–2019
Arsenic
3.2 µg/L 32%
of the EPA limit 10 µg/L
1/8 SYR4 2014–2017
91 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JOHN POLLEY
Phone
772-221-1442

Frequently asked questions about Martin Co Utilities

Is Martin Co Utilities tap water safe to drink?

EPA monitoring detected 9 contaminants in Martin Co Utilities's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Martin Co Utilities's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Martin Co Utilities serve?

Martin Co Utilities reports serving 104,105 people in Florida, per its EPA record.

Has Martin Co Utilities had any water quality violations?

The EPA has 54 violations on file for Martin Co Utilities, of which 11 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.