← Florida

Tap water quality report

Altamonte Springs Water Dept (2 Wps)

EPA monitoring tested this supplier for 98 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
16
detected
51,000
people served
3
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Seminole

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

3
health-based violations
29
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2004-04-01 → 2004-04-30
MCL Health-based Resolved 2004-04-01 → 2004-04-30
MCL Health-based Resolved 2004-04-01 → 2004-04-30
MON Monitoring Archived 2025-08-01 → 2025-08-31
MON Monitoring Archived 2025-05-01 → 2025-05-31
MON Monitoring Resolved 2019-11-01 → 2019-11-30
MON Monitoring Resolved 2019-11-01 → 2019-11-30
MON Monitoring Resolved 2019-11-01 → 2019-11-30
Other Monitoring Resolved 2016-08-10
MR Monitoring Archived 2001-06-01 → 2001-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFHXS 0.0038 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
63.425 µg/L 79%
of the EPA limit 80 µg/L
worst single sample: 77.75 µg/L
106/106 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
40.2075 µg/L 67%
of the EPA limit 60 µg/L
worst single sample: 50.6 µg/L
106/106 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Nitrate
14 µg/L 0.1%
of the EPA limit 10000 µg/L
12/32 SYR4 2012–2019
Fluoride
740 µg/L 19%
of the EPA limit 4000 µg/L
8/8 SYR4 2014–2017
Barium
8.715 µg/L 0.4%
of the EPA limit 2000 µg/L
worst single sample: 9 µg/L
4/4 SYR4 2014–2017
Copper
6.365 µg/L 0.5%
of the EPA limit 1300 µg/L
worst single sample: 6.5 µg/L
4/4 SYR4 2014–2017
Dalapon
1.185 µg/L 0.6%
of the EPA limit 200 µg/L
worst single sample: 1.2 µg/L
4/8 SYR4 2014–2017
Lead
0.3900 µg/L 2.6%
of the EPA limit 15 µg/L
worst single sample: 0.4000 µg/L
2/4 SYR4 2014–2017
Selenium
2.34 µg/L 4.7%
of the EPA limit 50 µg/L
worst single sample: 2.4 µg/L
2/4 SYR4 2014–2017
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
1/4 SYR4 2014–2017
Benzo(A)Pyrene
0.0200 µg/L 10%
of the EPA limit 0.2000 µg/L
1/8 SYR4 2014–2017
Beryllium, Total
0.2000 µg/L 5%
of the EPA limit 4 µg/L
1/4 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
0.4400 µg/L 7.3%
of the EPA limit 6 µg/L
1/12 SYR4 2012–2017
Thallium, Total
0.4000 µg/L 20%
of the EPA limit 2 µg/L
1/4 SYR4 2014–2017
82 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BRUCE DOIG
Phone
407-571-8538

Frequently asked questions about Altamonte Springs Water Dept (2 Wps)

Is Altamonte Springs Water Dept (2 Wps) tap water safe to drink?

EPA monitoring detected 16 contaminants in Altamonte Springs Water Dept (2 Wps)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Altamonte Springs Water Dept (2 Wps)'s water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Altamonte Springs Water Dept (2 Wps) serve?

Altamonte Springs Water Dept (2 Wps) reports serving 51,000 people in Florida, per its EPA record.

Has Altamonte Springs Water Dept (2 Wps) had any water quality violations?

The EPA has 29 violations on file for Altamonte Springs Water Dept (2 Wps), of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.