Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2016-08-01 → 2016-08-31 |
| MON | Monitoring | Resolved | 2016-08-01 → 2016-08-31 |
| Other | Monitoring | Resolved | 2006-05-29 |
| Other | Monitoring | Resolved | 2006-05-29 |
| Other | Monitoring | Resolved | 2006-05-29 |
| MR | Monitoring | Unaddressed | 2005-06-01 |
| Other | Monitoring | Resolved | 2003-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 730 µg/L 7.3% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Total Haloacetic Acids (HAA5) | 3.258 µg/L 5.4% of the EPA limit 60 µg/L
worst single sample: 3.36 µg/L | 4/7 | SYR4 | 2012–2019 |
| Arsenic | 0.6900 µg/L 6.9% of the EPA limit 10 µg/L
worst single sample: 0.7000 µg/L | 3/3 | SYR4 | 2012–2018 |
| Barium | 5.67 µg/L 0.3% of the EPA limit 2000 µg/L
worst single sample: 5.7 µg/L | 3/3 | SYR4 | 2012–2018 |
| Antimony, Total | 0.3900 µg/L 6.5% of the EPA limit 6 µg/L
worst single sample: 0.4000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Copper | 8.78 µg/L 0.7% of the EPA limit 1300 µg/L
worst single sample: 9.2 µg/L | 2/3 | SYR4 | 2012–2018 |
| Selenium | 2.07 µg/L 4.1% of the EPA limit 50 µg/L
worst single sample: 2.1 µg/L | 2/3 | SYR4 | 2012–2018 |
| TTHM | 10.3645 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 10.85 µg/L | 2/7 | SYR4 | 2012–2019 |
| Thallium, Total | 0.2900 µg/L 14% of the EPA limit 2 µg/L
worst single sample: 0.3000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Chromium | 0.7000 µg/L 0.7% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2018 |
| Lead | 0.3000 µg/L 2% of the EPA limit 15 µg/L | 1/3 | SYR4 | 2012–2018 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Silver Springs Woods/Village
Is Silver Springs Woods/Village tap water safe to drink?
EPA monitoring detected 12 contaminants in Silver Springs Woods/Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Silver Springs Woods/Village's water?
EPA monitoring detected Nitrate, Lead, Total Haloacetic Acids (HAA5), Arsenic, Barium, and others. The full list with the level and data source for each is above.
How many people does Silver Springs Woods/Village serve?
Silver Springs Woods/Village reports serving 852 people in Florida, per its EPA record.
Has Silver Springs Woods/Village had any water quality violations?
The EPA has 7 violations on file for Silver Springs Woods/Village, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.