← Florida

Tap water quality report

Melbourne, City of

EPA monitoring tested this supplier for 101 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

101
contaminants tested
15
detected
167,753
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Brevard

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
34
violations on file
0
still open
ViolationTypeStatusPeriod
MON Monitoring Archived 2025-09-01 → 2025-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
MR Monitoring Resolved 2023-07-01 → 2023-09-30
Other Monitoring Resolved 2003-07-01
MR Monitoring Archived 1999-08-01 → 1999-08-31
MR Monitoring Archived 1996-07-01 → 1996-07-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0090 µg/L 3/4 2024
PFBS 0.0040 µg/L 3/4 2024
Pfpea 0.0031 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
47.7 µg/L 60%
of the EPA limit 80 µg/L
worst single sample: 65.3 µg/L
195/195 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
44.71 µg/L 75%
of the EPA limit 60 µg/L
worst single sample: 91.3 µg/L
195/197 SYR4 2012–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
17/17 LCR 2023
Fluoride
810 µg/L 20%
of the EPA limit 4000 µg/L
16/16 SYR4 2012–2019
Nitrate
350 µg/L 3.5%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Barium
21.78 µg/L 1.1%
of the EPA limit 2000 µg/L
worst single sample: 22.2 µg/L
8/8 SYR4 2012–2019
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
1/8 SYR4 2012–2019
Cyanide
51.3 µg/L 26%
of the EPA limit 200 µg/L
1/9 SYR4 2012–2019
Diquat
0.3300 µg/L 1.7%
of the EPA limit 20 µg/L
1/8 SYR4 2014–2019
Nitrate-Nitrite
116 µg/L 1.2%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
Nitrite
83 µg/L 8.3%
of the EPA limit 1000 µg/L
1/8 SYR4 2012–2019
Selenium
3.2 µg/L 6.4%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DAVID PHARES
Phone
321-255-4622

Frequently asked questions about Melbourne, City of

Is Melbourne, City of tap water safe to drink?

EPA monitoring detected 15 contaminants in Melbourne, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Melbourne, City of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Fluoride, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Melbourne, City of serve?

Melbourne, City of reports serving 167,753 people in Florida, per its EPA record.

Has Melbourne, City of had any water quality violations?

The EPA has 34 violations on file for Melbourne, City of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.