Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Archived | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1997-03-01 → 1997-03-31 |
| MCL | Health-based | Archived | 1997-03-01 → 1997-03-31 |
| MCL | Health-based | Archived | 1997-03-01 → 1997-03-31 |
| Other | Monitoring | Resolved | 2024-07-01 |
| MR | Monitoring | Resolved | 2023-01-01 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2021-01-01 → 2021-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 27.668 µg/L 35% of the EPA limit 80 µg/L
worst single sample: 32.94 µg/L | 27/27 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 31.28 µg/L 52% of the EPA limit 60 µg/L
worst single sample: 39.42 µg/L | 25/25 | SYR4 | 2012–2018 |
| Barium | 26.5 µg/L 1.3% of the EPA limit 2000 µg/L
worst single sample: 31 µg/L | 19/19 | SYR4 | 2012–2017 |
| Lead | 0.0013 mg/L 8.7% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Fluoride | 436 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 520 µg/L | 15/25 | SYR4 | 2012–2017 |
| Nitrate | 180 µg/L 1.8% of the EPA limit 10000 µg/L | 12/74 | SYR4 | 2012–2019 |
| Antimony, Total | 2.915 µg/L 49% of the EPA limit 6 µg/L
worst single sample: 3.5 µg/L | 10/17 | SYR4 | 2012–2017 |
| Selenium | 4.6 µg/L 9.2% of the EPA limit 50 µg/L | 5/19 | SYR4 | 2012–2017 |
| Arsenic | 0.5550 µg/L 5.6% of the EPA limit 10 µg/L
worst single sample: 0.6000 µg/L | 4/19 | SYR4 | 2012–2017 |
| Copper | 0.6700 µg/L 0.1% of the EPA limit 1300 µg/L
worst single sample: 0.7000 µg/L | 4/7 | SYR4 | 2014–2017 |
| Lead | 7.72 µg/L 51% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 3/16 | SYR4 | 2012–2017 |
| Chromium | 0.4000 µg/L 0.4% of the EPA limit 100 µg/L | 2/19 | SYR4 | 2012–2017 |
| Thallium, Total | 0.1950 µg/L 9.8% of the EPA limit 2 µg/L
worst single sample: 0.2000 µg/L | 2/19 | SYR4 | 2012–2017 |
| Dalapon | 11 µg/L 5.5% of the EPA limit 200 µg/L | 1/29 | SYR4 | 2012–2019 |
| Nitrite | 100 µg/L 10% of the EPA limit 1000 µg/L | 1/37 | SYR4 | 2012–2019 |
| Lithium | 9.3 µg/L No EPA limit set | 1/3 | UCMR-5 | 2025 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Palm Coast Utility
Is City of Palm Coast Utility tap water safe to drink?
EPA monitoring detected 16 contaminants in City of Palm Coast Utility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Palm Coast Utility's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Barium, Lead, Fluoride, and others. The full list with the level and data source for each is above.
How many people does City of Palm Coast Utility serve?
City of Palm Coast Utility reports serving 112,324 people in Florida, per its EPA record.
Has City of Palm Coast Utility had any water quality violations?
The EPA has 11 violations on file for City of Palm Coast Utility, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.