← Florida

Tap water quality report

Lake Asbury Grid

EPA monitoring tested this supplier for 98 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
12
detected
27,001
people served
2
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Clay

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
3
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1997-02-01 → 1997-02-28
MCL Health-based Archived 1996-06-01 → 1996-06-30
MR Monitoring Archived 1984-04-01 → 1988-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
17.4965 µg/L 22%
of the EPA limit 80 µg/L
worst single sample: 54.62 µg/L
24/24 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
7.147 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 12.55 µg/L
22/24 SYR4 2014–2019
Lead
0.00070 mg/L 4.7%
of the EPA limit 0.0150 mg/L
12/12 LCR 2023
Fluoride
140 µg/L 3.5%
of the EPA limit 4000 µg/L
4/4 SYR4 2014–2017
Nitrate
100 µg/L 1%
of the EPA limit 10000 µg/L
4/20 SYR4 2012–2019
Barium
10 µg/L 0.5%
of the EPA limit 2000 µg/L
2/2 SYR4 2014–2017
Antimony, Total
0.1000 µg/L 1.7%
of the EPA limit 6 µg/L
1/2 SYR4 2014–2017
Arsenic
0.2000 µg/L 2%
of the EPA limit 10 µg/L
1/2 SYR4 2014–2017
Copper
0.5000 µg/L 0%
of the EPA limit 1300 µg/L
1/2 SYR4 2014–2017
Cadmium
0.1000 µg/L 2%
of the EPA limit 5 µg/L
1/2 SYR4 2014–2017
Lead
1.2 µg/L 8%
of the EPA limit 15 µg/L
1/2 SYR4 2014–2017
Thallium, Total
0.2000 µg/L 10%
of the EPA limit 2 µg/L
1/2 SYR4 2014–2017
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MR. JEREMY JOHNSTON, PE
Phone
904-213-2477

Frequently asked questions about Lake Asbury Grid

Is Lake Asbury Grid tap water safe to drink?

EPA monitoring detected 12 contaminants in Lake Asbury Grid's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lake Asbury Grid's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Fluoride, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Lake Asbury Grid serve?

Lake Asbury Grid reports serving 27,001 people in Florida, per its EPA record.

Has Lake Asbury Grid had any water quality violations?

The EPA has 3 violations on file for Lake Asbury Grid, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.