← Florida

Tap water quality report

Camp Blanding Joint Training Center

EPA monitoring tested this supplier for 69 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

69
contaminants tested
15
detected
900
people served
14
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Clay

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
44
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2012-09-01 → 2012-09-30
MCL Health-based Archived 2012-09-01 → 2012-09-30
MCL Health-based Archived 2008-09-01 → 2008-09-30
MCL Health-based Archived 2008-09-01 → 2008-09-30
MCL Health-based Archived 2006-10-01 → 2006-10-31
MCL Health-based Archived 2006-10-01 → 2006-10-31
MCL Health-based Archived 2005-06-01 → 2005-06-30
MCL Health-based Archived 1999-09-01 → 1999-09-30
MCL Health-based Archived 1997-11-01 → 1997-11-30
MCL Health-based Archived 1997-09-01 → 1997-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
160 µg/L 4%
of the EPA limit 4000 µg/L
worst single sample: 200 µg/L
24/24 SYR4 2012–2019
Lead
0.0014 mg/L 9.3%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
TTHM
38.978 µg/L 49%
of the EPA limit 80 µg/L
worst single sample: 39.35 µg/L
13/13 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
15.872 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 19.31 µg/L
13/13 SYR4 2012–2018
Barium
19 µg/L 1%
of the EPA limit 2000 µg/L
12/12 SYR4 2012–2018
Arsenic
1.965 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2.1 µg/L
10/12 SYR4 2012–2018
Copper
56.575 µg/L 4.4%
of the EPA limit 1300 µg/L
worst single sample: 83 µg/L
8/11 SYR4 2012–2019
Lead
20.97 µg/L 140%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 27 µg/L
7/16 SYR4 2012–2018
Cadmium
0.4800 µg/L 9.6%
of the EPA limit 5 µg/L
worst single sample: 0.5000 µg/L
5/12 SYR4 2012–2018
Selenium
5.52 µg/L 11%
of the EPA limit 50 µg/L
worst single sample: 5.6 µg/L
5/12 SYR4 2012–2018
Antimony, Total
0.4700 µg/L 7.8%
of the EPA limit 6 µg/L
worst single sample: 0.5000 µg/L
4/12 SYR4 2012–2018
Chromium
0.4850 µg/L 0.5%
of the EPA limit 100 µg/L
worst single sample: 0.5000 µg/L
4/12 SYR4 2012–2018
Thallium, Total
0.1000 µg/L 5%
of the EPA limit 2 µg/L
3/12 SYR4 2012–2018
Nitrate
19 µg/L 0.2%
of the EPA limit 10000 µg/L
2/80 SYR4 2012–2019
Nitrite
31.9 µg/L 3.2%
of the EPA limit 1000 µg/L
worst single sample: 32 µg/L
2/40 SYR4 2012–2019
54 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PHILLIP WILLARD
Phone
904-682-3506

Frequently asked questions about Camp Blanding Joint Training Center

Is Camp Blanding Joint Training Center tap water safe to drink?

EPA monitoring detected 15 contaminants in Camp Blanding Joint Training Center's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Camp Blanding Joint Training Center's water?

EPA monitoring detected Fluoride, Lead, TTHM, Total Haloacetic Acids (HAA5), Barium, and others. The full list with the level and data source for each is above.

How many people does Camp Blanding Joint Training Center serve?

Camp Blanding Joint Training Center reports serving 900 people in Florida, per its EPA record.

Has Camp Blanding Joint Training Center had any water quality violations?

The EPA has 44 violations on file for Camp Blanding Joint Training Center, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.