← Florida

Tap water quality report

Wakulla Water System (Riversink)

EPA monitoring tested this supplier for 69 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

69
contaminants tested
18
detected
216
people served
8
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Wakulla

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
14
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2021-01-01 → 2021-03-31
MCL Health-based Resolved 2021-01-01 → 2021-03-31
MCL Health-based Resolved 2021-01-01 → 2021-03-31
MR Monitoring Unaddressed 2022-01-01
MR Monitoring Archived 2020-10-01 → 2020-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
84.35 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 101 µg/L
19/20 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
57.17 µg/L 95%
of the EPA limit 60 µg/L
worst single sample: 68.6 µg/L
19/20 SYR4 2012–2019
Nitrate
364 µg/L 3.6%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Fluoride
180 µg/L 4.5%
of the EPA limit 4000 µg/L
6/6 SYR4 2012–2018
Xylenes, Total
1.455 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 1.54 µg/L
6/16 SYR4 2012–2019
Barium
27.9 µg/L 1.4%
of the EPA limit 2000 µg/L
worst single sample: 28 µg/L
3/3 SYR4 2012–2018
Copper
10.32 µg/L 0.8%
of the EPA limit 1300 µg/L
worst single sample: 11 µg/L
3/3 SYR4 2012–2018
Chromium
9.25 µg/L 9.3%
of the EPA limit 100 µg/L
worst single sample: 10 µg/L
3/3 SYR4 2012–2018
Arsenic
6.635 µg/L 66%
of the EPA limit 10 µg/L
worst single sample: 6.7 µg/L
2/3 SYR4 2012–2018
1,2-Dichloroethane
0.8200 µg/L 16%
of the EPA limit 5 µg/L
1/16 SYR4 2012–2019
Antimony, Total
0.2000 µg/L 3.3%
of the EPA limit 6 µg/L
1/3 SYR4 2012–2018
Cadmium
1 µg/L 20%
of the EPA limit 5 µg/L
1/3 SYR4 2012–2018
Combined Uranium
9.685 µg/L 32%
of the EPA limit 30 µg/L
1/1 SYR4 2015
Ethylbenzene
0.4200 µg/L 0.1%
of the EPA limit 700 µg/L
1/16 SYR4 2012–2019
Lead
0.9000 µg/L 6%
of the EPA limit 15 µg/L
1/3 SYR4 2012–2018
Nitrite
100 µg/L 10%
of the EPA limit 1000 µg/L
1/9 SYR4 2012–2019
Selenium
1.3 µg/L 2.6%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
51 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JOHN HALLAS
Phone
850-562-2115

Frequently asked questions about Wakulla Water System (Riversink)

Is Wakulla Water System (Riversink) tap water safe to drink?

EPA monitoring detected 18 contaminants in Wakulla Water System (Riversink)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wakulla Water System (Riversink)'s water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Wakulla Water System (Riversink) serve?

Wakulla Water System (Riversink) reports serving 216 people in Florida, per its EPA record.

Has Wakulla Water System (Riversink) had any water quality violations?

The EPA has 14 violations on file for Wakulla Water System (Riversink), of which 8 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.