Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1997-07-01 → 1997-09-30 |
| MR | Monitoring | Resolved | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Resolved | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Resolved | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Resolved | 2015-12-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-12-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFHXS | 0.0553 µg/L | 25/54 | 2024 |
| Pfpea | 0.1389 µg/L | 25/54 | 2024 |
| PFOA | 0.0258 µg/L | 24/54 | 2024 |
| PFOS | 0.0357 µg/L | 21/54 | 2024 |
| Pfhxa | 0.1110 µg/L | 19/54 | 2024 |
| PFBS | 0.0160 µg/L | 15/54 | 2024 |
| Pfhpa | 0.0378 µg/L | 14/54 | 2024 |
| 6:2 Fts | 0.2201 µg/L | 4/54 | 2024 |
| PFNA | 0.0162 µg/L | 2/54 | 2024 |
| Pfpes | 0.0110 µg/L | 2/54 | 2024 |
| 4:2 Fts | 0.0076 µg/L | 1/54 | 2024 |
| Pfba | 0.0407 µg/L | 1/54 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 3445 µg/L 34% of the EPA limit 10000 µg/L
worst single sample: 4200 µg/L | 438/440 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 2.3055 µg/L 46% of the EPA limit 5 µg/L
worst single sample: 4.59 µg/L | 110/433 | SYR4 | 2012–2019 |
| Fluoride | 800 µg/L 20% of the EPA limit 4000 µg/L | 92/112 | SYR4 | 2014–2017 |
| TTHM | 10.6 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 12.9 µg/L | 63/72 | SYR4 | 2012–2019 |
| Barium | 52.5 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 56 µg/L | 56/56 | SYR4 | 2014–2017 |
| Trichloroethylene | 1.3535 µg/L 27% of the EPA limit 5 µg/L
worst single sample: 2.31 µg/L | 48/433 | SYR4 | 2012–2019 |
| Copper | 5.41 µg/L 0.4% of the EPA limit 1300 µg/L
worst single sample: 24 µg/L | 39/56 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 6.612 µg/L 11% of the EPA limit 60 µg/L
worst single sample: 15.88 µg/L | 37/70 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 1.0165 µg/L 15% of the EPA limit 7 µg/L
worst single sample: 1.09 µg/L | 28/433 | SYR4 | 2012–2019 |
| Selenium | 2.035 µg/L 4.1% of the EPA limit 50 µg/L
worst single sample: 2.7 µg/L | 20/56 | SYR4 | 2014–2017 |
| Chromium | 2.7 µg/L 2.7% of the EPA limit 100 µg/L
worst single sample: 4.8 µg/L | 16/56 | SYR4 | 2014–2017 |
| Lead | 0.00060 mg/L 4% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2023 |
| cis-1,2-Dichloroethylene | 0.3525 µg/L 0.5% of the EPA limit 70 µg/L
worst single sample: 0.3900 µg/L | 16/433 | SYR4 | 2012–2019 |
| Cyanide | 14.8 µg/L 7.4% of the EPA limit 200 µg/L
worst single sample: 16 µg/L | 13/56 | SYR4 | 2014–2017 |
| Beryllium, Total | 0.4200 µg/L 11% of the EPA limit 4 µg/L
worst single sample: 0.5000 µg/L | 9/56 | SYR4 | 2014–2017 |
| Arsenic | 1.72 µg/L 17% of the EPA limit 10 µg/L
worst single sample: 1.8 µg/L | 5/56 | SYR4 | 2014–2017 |
| Di(2-ethylhexyl) Phthalate | 0.8000 µg/L 13% of the EPA limit 6 µg/L | 4/70 | SYR4 | 2014–2017 |
| Dichloromethane | 0.4315 µg/L 8.6% of the EPA limit 5 µg/L
worst single sample: 0.4400 µg/L | 2/433 | SYR4 | 2012–2019 |
| Styrene | 1.338 µg/L 1.3% of the EPA limit 100 µg/L
worst single sample: 1.34 µg/L | 2/433 | SYR4 | 2012–2019 |
| Chlorobenzene | 0.6000 µg/L 0.6% of the EPA limit 100 µg/L | 1/433 | SYR4 | 2012–2019 |
| Mercury | 0.1000 µg/L 5% of the EPA limit 2 µg/L | 1/57 | SYR4 | 2014–2017 |
| Xylenes, Total | 0.8400 µg/L 0% of the EPA limit 10000 µg/L | 1/433 | SYR4 | 2012–2019 |
64 contaminants tested, none detected
Utility contact
Frequently asked questions about Emerald Coast Utilities Authority (Ecua)
Is Emerald Coast Utilities Authority (Ecua) tap water safe to drink?
EPA monitoring detected 34 contaminants in Emerald Coast Utilities Authority (Ecua)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Emerald Coast Utilities Authority (Ecua)'s water?
EPA monitoring detected Nitrate, Tetrachloroethylene, Fluoride, TTHM, Barium, and others. The full list with the level and data source for each is above.
How many people does Emerald Coast Utilities Authority (Ecua) serve?
Emerald Coast Utilities Authority (Ecua) reports serving 242,172 people in Florida, per its EPA record.
Has Emerald Coast Utilities Authority (Ecua) had any water quality violations?
The EPA has 14 violations on file for Emerald Coast Utilities Authority (Ecua), of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.