← Delaware

Tap water quality report

Fox Pointe Subdivision

EPA monitoring tested this supplier for 51 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

51
contaminants tested
17
detected
500
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Kent

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
15
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
Other Monitoring Resolved 2022-07-01
Other Monitoring Resolved 2022-07-01
MR Monitoring Resolved 2018-10-01
MR Monitoring Resolved 2018-10-01
MR Monitoring Resolved 2018-10-01
Other Monitoring Resolved 2018-07-01
Other Monitoring Resolved 2018-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
254 µg/L 20%
of the EPA limit 1300 µg/L
worst single sample: 470 µg/L
25/30 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
12/12 LCR 2025
Lead
48.69 µg/L 325%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 66 µg/L
7/31 SYR4 2012–2019
Fluoride
123.45 µg/L 3.1%
of the EPA limit 4000 µg/L
worst single sample: 124.6 µg/L
6/8 SYR4 2012–2019
Bromodichloromethane
3.302 µg/L
No EPA limit set
worst single sample: 3.62 µg/L
4/4 SYR4 2012–2018
Dibromochloromethane
3.391 µg/L
No EPA limit set
worst single sample: 3.73 µg/L
4/4 SYR4 2012–2018
Chloroform
2.673 µg/L
No EPA limit set
worst single sample: 2.74 µg/L
3/4 SYR4 2012–2018
Dibromoacetic Acid
1.47785 µg/L
No EPA limit set
worst single sample: 1.52 µg/L
2/2 SYR4 2014–2017
Dichloroacetic Acid
1.25705 µg/L
No EPA limit set
worst single sample: 1.29 µg/L
2/2 SYR4 2014–2017
TTHM
9.928 µg/L 12%
of the EPA limit 80 µg/L
worst single sample: 10.29 µg/L
2/2 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
2.75535 µg/L 4.6%
of the EPA limit 60 µg/L
worst single sample: 2.81 µg/L
2/2 SYR4 2014–2017
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
1/1 SYR4 2015
Bromoform
0.8700 µg/L
No EPA limit set
1/4 SYR4 2012–2018
Chromium
4.9 µg/L 4.9%
of the EPA limit 100 µg/L
1/1 SYR4 2015
Combined Radium (-226 And -228)
1.168 pCi/L 23%
of the EPA limit 5 pCi/L
1/1 SYR4 2016
Monobromoacetic Acid
0.0980 µg/L
No EPA limit set
1/2 SYR4 2014–2017
Trichloroacetic Acid
0.3110 µg/L
No EPA limit set
1/2 SYR4 2014–2017
34 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBariumBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidNitrateNitrate-NitriteNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DAVISON, PAT
Phone
302-270-4666
Email
[email protected]

Frequently asked questions about Fox Pointe Subdivision

Is Fox Pointe Subdivision tap water safe to drink?

EPA monitoring detected 17 contaminants in Fox Pointe Subdivision's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Fox Pointe Subdivision's water?

EPA monitoring detected Copper, Lead, Lead, Fluoride, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Fox Pointe Subdivision serve?

Fox Pointe Subdivision reports serving 500 people in Delaware, per its EPA record.

Has Fox Pointe Subdivision had any water quality violations?

The EPA has 15 violations on file for Fox Pointe Subdivision, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.