Tap water quality report

Pinewood Acres

EPA monitoring tested this supplier for 75 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
14
detected
1,200
people served
9
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Kent

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

9
health-based violations
22
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Archived 1993-01-01 → 1993-03-31
MCL Health-based Archived 1993-01-01 → 1993-03-31
MCL Health-based Resolved 1992-07-01 → 1992-09-30
MCL Health-based Resolved 1992-07-01 → 1992-09-30
MCL Health-based Archived 1992-07-01 → 1992-09-30
Other Monitoring Resolved 2013-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
135.86 µg/L 3.4%
of the EPA limit 4000 µg/L
worst single sample: 140 µg/L
13/16 SYR4 2012–2019
Copper
14.8 µg/L 1.1%
of the EPA limit 1300 µg/L
worst single sample: 15.5 µg/L
11/13 SYR4 2012–2018
Chloroform
2.8575 µg/L
No EPA limit set
worst single sample: 2.98 µg/L
8/9 SYR4 2012–2019
TTHM
3.76 µg/L 4.7%
of the EPA limit 80 µg/L
worst single sample: 4.2 µg/L
5/5 SYR4 2014–2019
Bromodichloromethane
1.2545 µg/L
No EPA limit set
worst single sample: 1.31 µg/L
4/9 SYR4 2012–2019
Lead
0.00044 mg/L 2.9%
of the EPA limit 0.0150 mg/L
3/3 LCR 2021
Chromium
2.395 µg/L 2.4%
of the EPA limit 100 µg/L
worst single sample: 2.4 µg/L
2/4 SYR4 2012–2018
Combined Radium (-226 And -228)
0.9281 pCi/L 19%
of the EPA limit 5 pCi/L
worst single sample: 0.9350 pCi/L
2/2 SYR4 2014
Dichloroacetic Acid
1.1 µg/L
No EPA limit set
2/5 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
1.765 µg/L 2.9%
of the EPA limit 60 µg/L
worst single sample: 1.8 µg/L
2/5 SYR4 2014–2019
Dibromoacetic Acid
0.2000 µg/L
No EPA limit set
1/5 SYR4 2014–2019
Dibromochloromethane
0.6000 µg/L
No EPA limit set
1/9 SYR4 2012–2019
Lead
0.6000 µg/L 4%
of the EPA limit 15 µg/L
1/14 SYR4 2012–2018
Trichloroacetic Acid
0.5000 µg/L
No EPA limit set
1/5 SYR4 2014–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitrateNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about Pinewood Acres

Is Pinewood Acres tap water safe to drink?

EPA monitoring detected 14 contaminants in Pinewood Acres's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Pinewood Acres's water?

EPA monitoring detected Fluoride, Copper, Chloroform, TTHM, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Pinewood Acres serve?

Pinewood Acres reports serving 1,200 people, per its EPA record.

Has Pinewood Acres had any water quality violations?

The EPA has 22 violations on file for Pinewood Acres, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.