Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2024-10-01 |
| MR | Monitoring | Resolved | 2024-10-01 |
| MR | Monitoring | Resolved | 2024-10-01 |
| Other | Monitoring | Resolved | 2024-07-10 |
| Other | Monitoring | Resolved | 2024-07-10 |
| Other | Monitoring | Resolved | 2022-07-01 |
| Other | Monitoring | Resolved | 2022-07-01 |
| Other | Monitoring | Resolved | 2000-07-01 → 2000-10-13 |
| Other | Monitoring | Resolved | 1999-10-19 |
| Other | Monitoring | Resolved | 1999-10-19 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 23.08 µg/L No EPA limit set
worst single sample: 23.6 µg/L | 14/14 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.735 µg/L No EPA limit set
worst single sample: 9.29 µg/L | 11/14 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.949 µg/L No EPA limit set
worst single sample: 2.18 µg/L | 8/14 | SYR4 | 2012–2019 |
| Copper | 56.75 µg/L 4.4% of the EPA limit 1300 µg/L
worst single sample: 57 µg/L | 6/6 | SYR4 | 2015 |
| Combined Radium (-226 And -228) | 0.6390 pCi/L 13% of the EPA limit 5 pCi/L
worst single sample: 0.6490 pCi/L | 6/7 | SYR4 | 2013–2015 |
| Dichloroacetic Acid | 14.354 µg/L No EPA limit set
worst single sample: 15.672 µg/L | 6/6 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 30.2578 µg/L 50% of the EPA limit 60 µg/L
worst single sample: 31.677 µg/L | 6/6 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 15.371 µg/L No EPA limit set
worst single sample: 16 µg/L | 6/6 | SYR4 | 2014–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 5/5 | LCR | 2025 |
| TTHM | 33.76 µg/L 42% of the EPA limit 80 µg/L
worst single sample: 34.3 µg/L | 4/4 | SYR4 | 2015–2019 |
| Fluoride | 54.15 µg/L 1.4% of the EPA limit 4000 µg/L
worst single sample: 54.2 µg/L | 3/22 | SYR4 | 2012–2019 |
| Lead | 3.18 µg/L 21% of the EPA limit 15 µg/L
worst single sample: 3.2 µg/L | 3/6 | SYR4 | 2015 |
| Monochloroacetic Acid | 2.46295 µg/L No EPA limit set
worst single sample: 2.521 µg/L | 2/6 | SYR4 | 2014–2019 |
| Nitrate | 10224.6 µg/L 102% of the EPA limit, at the 95th percentile of samples — 10000 µg/L | 2/44 | SYR4 | 2012–2019 |
| Vinyl Chloride | 0.7580 µg/L 38% of the EPA limit 2 µg/L
worst single sample: 0.7600 µg/L | 2/14 | SYR4 | 2012–2019 |
| Barium | 26 µg/L 1.3% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2015 |
| Chromium | 1.7 µg/L 1.7% of the EPA limit 100 µg/L | 1/1 | SYR4 | 2015 |
| Nitrate-Nitrite | 10224.6 µg/L 102% of the EPA limit, at the 95th percentile of samples — 10000 µg/L | 1/22 | SYR4 | 2012–2019 |
| Styrene | 0.5300 µg/L 0.5% of the EPA limit 100 µg/L | 1/14 | SYR4 | 2012–2019 |
| Toluene | 5.21 µg/L 0.5% of the EPA limit 1000 µg/L | 1/14 | SYR4 | 2012–2019 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Cape Windsor Community Association Inc
Is Cape Windsor Community Association Inc tap water safe to drink?
EPA monitoring detected 20 contaminants in Cape Windsor Community Association Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cape Windsor Community Association Inc's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Dibromochloromethane, Copper, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.
How many people does Cape Windsor Community Association Inc serve?
Cape Windsor Community Association Inc reports serving 600 people in Delaware, per its EPA record.
Has Cape Windsor Community Association Inc had any water quality violations?
The EPA has 22 violations on file for Cape Windsor Community Association Inc, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.