Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2009-07-01 → 2009-12-31 |
| MR | Monitoring | Resolved | 2009-07-01 → 2009-12-31 |
| MR | Monitoring | Resolved | 2009-07-01 → 2009-12-31 |
| Other | Monitoring | Resolved | 2002-07-01 → 2002-07-25 |
| MR | Monitoring | Resolved | 1994-01-01 → 1995-09-05 |
| MR | Monitoring | Resolved | 1994-01-01 → 1995-09-05 |
| MR | Monitoring | Resolved | 1993-07-01 → 1995-09-05 |
| MR | Monitoring | Resolved | 1993-07-01 → 1995-09-05 |
| MR | Monitoring | Resolved | 1993-07-01 |
| MR | Monitoring | Resolved | 1993-07-01 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFOS | 0.0061 µg/L | 2/10 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 143.05 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 367 µg/L | 260/317 | SYR4 | 2012–2018 |
| Chloroform | 58.3975 µg/L No EPA limit set
worst single sample: 101 µg/L | 88/114 | SYR4 | 2012–2019 |
| Bromodichloromethane | 32.36 µg/L No EPA limit set
worst single sample: 53.5 µg/L | 85/114 | SYR4 | 2012–2019 |
| Dibromochloromethane | 13.385 µg/L No EPA limit set
worst single sample: 19 µg/L | 84/114 | SYR4 | 2012–2019 |
| TTHM | 105.15 µg/L 131% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 175 µg/L | 71/74 | SYR4 | 2012–2019 |
| Lead | 43.02 µg/L 287% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 59.9 µg/L | 65/318 | SYR4 | 2012–2018 |
| Bromoform | 4.002 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 58/114 | SYR4 | 2012–2019 |
| Nitrate | 5900 µg/L 59% of the EPA limit 10000 µg/L | 52/82 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 69.5528 µg/L 116% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 76.973 µg/L | 48/61 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.26 µg/L No EPA limit set
worst single sample: 5.6 µg/L | 43/61 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.4038 µg/L No EPA limit set
worst single sample: 35.1 µg/L | 40/61 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 34.642 µg/L No EPA limit set
worst single sample: 40.27 µg/L | 27/61 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 5900 µg/L 59% of the EPA limit 10000 µg/L | 26/41 | SYR4 | 2012–2019 |
| Lead | 0.0023 mg/L 15% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2023 |
| Monochloroacetic Acid | 5.64925 µg/L No EPA limit set
worst single sample: 9.4 µg/L | 16/61 | SYR4 | 2012–2019 |
| Barium | 96.62 µg/L 4.8% of the EPA limit 2000 µg/L
worst single sample: 98 µg/L | 13/14 | SYR4 | 2014–2018 |
| Combined Radium (-226 And -228) | 2.1 pCi/L 42% of the EPA limit 5 pCi/L
worst single sample: 2.2 pCi/L | 6/7 | SYR4 | 2013–2019 |
| Fluoride | 102.775 µg/L 2.6% of the EPA limit 4000 µg/L
worst single sample: 103.7 µg/L | 6/41 | SYR4 | 2012–2019 |
| Chromium | 3.74 µg/L 3.7% of the EPA limit 100 µg/L
worst single sample: 4 µg/L | 5/14 | SYR4 | 2014–2018 |
| Selenium | 0.6505 µg/L 1.3% of the EPA limit 50 µg/L
worst single sample: 0.6700 µg/L | 4/14 | SYR4 | 2014–2018 |
| Monobromoacetic Acid | 1.098 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/61 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 1.14 µg/L 23% of the EPA limit 5 µg/L
worst single sample: 1.16 µg/L | 2/98 | SYR4 | 2012–2019 |
| Xylenes, Total | 0.6050 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 0.6100 µg/L | 2/95 | SYR4 | 2012–2019 |
| 2,4-D | 0.0900 µg/L 0.1% of the EPA limit 70 µg/L | 1/27 | SYR4 | 2012–2019 |
| Arsenic | 4.39 µg/L 44% of the EPA limit 10 µg/L | 1/14 | SYR4 | 2014–2018 |
| Pentachlorophenol | 0.0320 µg/L 3.2% of the EPA limit 1 µg/L | 1/27 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Frequently asked questions about Bethany Bay Pump District
Is Bethany Bay Pump District tap water safe to drink?
EPA monitoring detected 27 contaminants in Bethany Bay Pump District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bethany Bay Pump District's water?
EPA monitoring detected Copper, Chloroform, Bromodichloromethane, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Bethany Bay Pump District serve?
Bethany Bay Pump District reports serving 51,000 people, per its EPA record.
Has Bethany Bay Pump District had any water quality violations?
The EPA has 10 violations on file for Bethany Bay Pump District, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.