Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1998-06-01 → 1998-06-30 |
| MCL | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
| MCL | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
| MCL | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
| MCL | Health-based | Resolved | 1993-08-01 → 1993-08-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 215 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 258 µg/L | 65/65 | SYR4 | 2014–2018 |
| Nitrate | 1790 µg/L 18% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.7 µg/L No EPA limit set | 12/17 | SYR4 | 2012–2019 |
| Lead | 0.00060 mg/L 4% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2024 |
| Bromodichloromethane | 6.115 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 10/17 | SYR4 | 2012–2019 |
| Bromoform | 4.935 µg/L No EPA limit set
worst single sample: 5.7 µg/L | 10/17 | SYR4 | 2012–2019 |
| Lead | 11.82 µg/L 79% of the EPA limit 15 µg/L
worst single sample: 13.8 µg/L | 10/65 | SYR4 | 2014–2018 |
| Chloroform | 5.22 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 9/17 | SYR4 | 2012–2019 |
| TTHM | 21.24 µg/L 27% of the EPA limit 80 µg/L
worst single sample: 23.2 µg/L | 9/9 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.93 µg/L No EPA limit set
worst single sample: 2 µg/L | 8/9 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1755 µg/L 18% of the EPA limit 10000 µg/L
worst single sample: 1790 µg/L | 8/8 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 3.65 µg/L 6.1% of the EPA limit 60 µg/L
worst single sample: 4 µg/L | 8/9 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2 µg/L No EPA limit set | 4/9 | SYR4 | 2012–2019 |
| Barium | 37 µg/L 1.9% of the EPA limit 2000 µg/L
worst single sample: 38 µg/L | 3/3 | SYR4 | 2014–2018 |
| Di(2-ethylhexyl) Phthalate | 1.2 µg/L 20% of the EPA limit 6 µg/L | 1/4 | SYR4 | 2013–2017 |
94 contaminants tested, none detected
Utility contact
Frequently asked questions about Ctwc - Naugatuck Reg-Terryville
Is Ctwc - Naugatuck Reg-Terryville tap water safe to drink?
EPA monitoring detected 15 contaminants in Ctwc - Naugatuck Reg-Terryville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ctwc - Naugatuck Reg-Terryville's water?
EPA monitoring detected Copper, Nitrate, Dibromochloromethane, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Ctwc - Naugatuck Reg-Terryville serve?
Ctwc - Naugatuck Reg-Terryville reports serving 5,607 people in Connecticut, per its EPA record.
Has Ctwc - Naugatuck Reg-Terryville had any water quality violations?
The EPA has 9 violations on file for Ctwc - Naugatuck Reg-Terryville, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.