Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2025-08-10 |
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2023-07-01 |
| MR | Monitoring | Resolved | 2020-08-01 → 2020-10-31 |
| MR | Monitoring | Resolved | 2020-08-01 → 2020-10-31 |
| MR | Monitoring | Resolved | 2020-08-01 → 2020-10-31 |
| MR | Monitoring | Resolved | 2020-08-01 → 2020-10-31 |
| MR | Monitoring | Archived | 2011-01-01 → 2011-03-31 |
| Other | Monitoring | Resolved | 2007-07-01 |
| Other | Monitoring | Resolved | 2007-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 13.8 µg/L No EPA limit set
worst single sample: 14.6 µg/L | 198/198 | SYR4 | 2012–2019 |
| Chloroform | 75.58 µg/L No EPA limit set
worst single sample: 103.4 µg/L | 198/198 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.32 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 197/198 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 22.17 µg/L No EPA limit set
worst single sample: 34.6 µg/L | 182/182 | SYR4 | 2012–2019 |
| TTHM | 92.635 µg/L 116% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 119.7 µg/L | 182/182 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 44.36 µg/L 74% of the EPA limit 60 µg/L
worst single sample: 61.8 µg/L | 182/182 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 22.39 µg/L No EPA limit set
worst single sample: 25.3 µg/L | 182/182 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.205 µg/L No EPA limit set
worst single sample: 3.1 µg/L | 140/182 | SYR4 | 2012–2019 |
| Copper | 174 µg/L 13% of the EPA limit 1300 µg/L
worst single sample: 270 µg/L | 107/112 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 34/34 | LCR | 2026 |
| Nitrate | 412.8 µg/L 4.1% of the EPA limit 10000 µg/L
worst single sample: 470 µg/L | 34/34 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 414.4 µg/L 4.1% of the EPA limit 10000 µg/L
worst single sample: 470 µg/L | 33/33 | SYR4 | 2012–2019 |
| Barium | 39.8 µg/L 2% of the EPA limit 2000 µg/L
worst single sample: 50 µg/L | 32/32 | SYR4 | 2012–2019 |
| Fluoride | 1017 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1090 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 0.9050 µg/L No EPA limit set
worst single sample: 1 µg/L | 20/182 | SYR4 | 2012–2019 |
| Lead | 28.4 µg/L 189% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 59 µg/L | 13/112 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 0.6850 µg/L No EPA limit set
worst single sample: 0.7000 µg/L | 4/182 | SYR4 | 2012–2019 |
| Arsenic | 4.8 µg/L 48% of the EPA limit 10 µg/L
worst single sample: 5 µg/L | 2/32 | SYR4 | 2012–2019 |
| Bromoform | 0.9750 µg/L No EPA limit set
worst single sample: 1 µg/L | 2/198 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.13 pCi/L 43% of the EPA limit 5 pCi/L | 1/7 | SYR4 | 2012–2018 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Middletown Water Department
Is Middletown Water Department tap water safe to drink?
EPA monitoring detected 20 contaminants in Middletown Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Middletown Water Department's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Middletown Water Department serve?
Middletown Water Department reports serving 41,019 people in Connecticut, per its EPA record.
Has Middletown Water Department had any water quality violations?
The EPA has 16 violations on file for Middletown Water Department, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.