← Colorado

Tap water quality report

Frisco Town of

EPA monitoring tested this supplier for 108 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
24
detected
4,495
people served
8
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Summit

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
812
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-08-30
TT Health-based Resolved 2021-08-30
TT Health-based Resolved 2021-08-30
TT Health-based Resolved 2021-08-30
MCL Health-based Resolved 2014-05-01 → 2014-05-31
MCL Health-based Resolved 2014-05-01 → 2014-05-31
MCL Health-based Resolved 2014-05-01 → 2014-05-31
MCL Health-based Resolved 2014-05-01 → 2014-05-31
MR Monitoring Resolved 2025-04-01 → 2025-04-30
MR Monitoring Resolved 2025-04-01 → 2025-04-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
56.38 µg/L 70%
of the EPA limit 80 µg/L
worst single sample: 86.9 µg/L
79/80 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
75.61 µg/L 126%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 124.7 µg/L
68/80 SYR4 2012–2019
Nitrate
910 µg/L 9.1%
of the EPA limit 10000 µg/L
worst single sample: 1000 µg/L
58/60 SYR4 2012–2019
Chloroform
47.76 µg/L
No EPA limit set
worst single sample: 82.4 µg/L
40/42 SYR4 2013–2019
Bromodichloromethane
4.265 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
38/42 SYR4 2013–2019
Dichloroacetic Acid
32.605 µg/L
No EPA limit set
worst single sample: 45.3 µg/L
34/39 SYR4 2015–2019
Trichloroacetic Acid
48.2 µg/L
No EPA limit set
worst single sample: 76.4 µg/L
31/39 SYR4 2015–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
26/26 LCR 2025
Barium
84.85 µg/L 4.2%
of the EPA limit 2000 µg/L
worst single sample: 88 µg/L
24/24 SYR4 2012–2019
Dibromochloromethane
3.085 µg/L
No EPA limit set
worst single sample: 3.3 µg/L
24/42 SYR4 2013–2019
Bromoform
1.004 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
15/42 SYR4 2013–2019
Chromium
3 µg/L 3%
of the EPA limit 100 µg/L
8/24 SYR4 2012–2019
Combined Uranium
2.65 µg/L 8.8%
of the EPA limit 30 µg/L
worst single sample: 3 µg/L
8/8 SYR4 2016–2019
Combined Radium (-226 And -228)
2.43 pCi/L 49%
of the EPA limit 5 pCi/L
worst single sample: 2.7 pCi/L
7/8 SYR4 2016–2019
Gross Alpha, Excl. Radon And U
2.171 pCi/L 14%
of the EPA limit 15 pCi/L
worst single sample: 2.36 pCi/L
7/8 SYR4 2016–2019
Monochloroacetic Acid
3.7 µg/L
No EPA limit set
worst single sample: 4 µg/L
7/39 SYR4 2015–2019
Selenium
5.5 µg/L 11%
of the EPA limit 50 µg/L
worst single sample: 7 µg/L
7/24 SYR4 2012–2019
Dibromoacetic Acid
1.86 µg/L
No EPA limit set
worst single sample: 2 µg/L
5/39 SYR4 2015–2019
Ethylene Dibromide
0.0385 µg/L 77%
of the EPA limit 0.0500 µg/L
worst single sample: 0.0400 µg/L
4/30 SYR4 2013–2019
Nitrate-Nitrite
600 µg/L 6%
of the EPA limit 10000 µg/L
4/4 SYR4 2016–2019
Fluoride
816 µg/L 20%
of the EPA limit 4000 µg/L
worst single sample: 830 µg/L
2/24 SYR4 2012–2019
Diquat
0.3500 µg/L 1.7%
of the EPA limit 20 µg/L
1/31 SYR4 2013–2019
Hexachlorobenzene
0.0093 µg/L 0.9%
of the EPA limit 1 µg/L
1/31 SYR4 2013–2019
Monobromoacetic Acid
3.2 µg/L
No EPA limit set
1/39 SYR4 2015–2019
84 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEndothallEndrinEthylbenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SOUTHWORTH, JOSH
Phone
970-668-9149
Email
[email protected]

Frequently asked questions about Frisco Town of

Is Frisco Town of tap water safe to drink?

EPA monitoring detected 24 contaminants in Frisco Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Frisco Town of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Chloroform, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Frisco Town of serve?

Frisco Town of reports serving 4,495 people in Colorado, per its EPA record.

Has Frisco Town of had any water quality violations?

The EPA has 812 violations on file for Frisco Town of, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.