← Colorado

Tap water quality report

Steamboat Ii Md

EPA monitoring tested this supplier for 76 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
19
detected
1,450
people served
18
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Routt

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

18
health-based violations
439
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2023-12-21
TT Health-based Resolved 2023-12-21
TT Health-based Resolved 2023-12-21
TT Health-based Resolved 2023-12-21
TT Health-based Resolved 2023-02-17
TT Health-based Resolved 2023-02-17
TT Health-based Resolved 2023-02-17
TT Health-based Resolved 2023-02-17
TT Health-based Resolved 2023-02-17
TT Health-based Resolved 2023-02-17

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
54.32 µg/L 68%
of the EPA limit 80 µg/L
worst single sample: 62.4 µg/L
57/57 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
60.575 µg/L 101%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 68.5 µg/L
54/55 SYR4 2012–2019
Nitrate
1300 µg/L 13%
of the EPA limit 10000 µg/L
14/16 SYR4 2012–2019
Lead
0.0082 mg/L 55%
of the EPA limit 0.0150 mg/L
12/12 LCR 2025
Bromodichloromethane
5.55 µg/L
No EPA limit set
worst single sample: 5.8 µg/L
6/6 SYR4 2016–2019
Chloroform
41.1 µg/L
No EPA limit set
worst single sample: 42.8 µg/L
6/6 SYR4 2016–2019
Dichloroacetic Acid
20.42 µg/L
No EPA limit set
worst single sample: 20.7 µg/L
5/6 SYR4 2016–2019
Trichloroacetic Acid
34.56 µg/L
No EPA limit set
worst single sample: 34.7 µg/L
5/6 SYR4 2016–2019
Barium
126.3 µg/L 6.3%
of the EPA limit 2000 µg/L
worst single sample: 130 µg/L
3/3 SYR4 2013–2019
Fluoride
178 µg/L 4.5%
of the EPA limit 4000 µg/L
worst single sample: 180 µg/L
3/3 SYR4 2013–2019
Monochloroacetic Acid
2.27 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
3/6 SYR4 2016–2019
Selenium
5.01 µg/L 10%
of the EPA limit 50 µg/L
worst single sample: 5.2 µg/L
3/3 SYR4 2013–2019
Cadmium
0.2855 µg/L 5.7%
of the EPA limit 5 µg/L
worst single sample: 0.2900 µg/L
2/3 SYR4 2013–2019
Dibromochloromethane
1.1855 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
2/6 SYR4 2016–2019
Antimony, Total
0.4200 µg/L 7%
of the EPA limit 6 µg/L
1/3 SYR4 2013–2019
Combined Uranium
0.0098 µg/L 0%
of the EPA limit 30 µg/L
1/1 SYR4 2019
Dibromoacetic Acid
1 µg/L
No EPA limit set
1/6 SYR4 2016–2019
Gross Alpha, Excl. Radon And U
9.993 pCi/L 67%
of the EPA limit 15 pCi/L
1/1 SYR4 2019
Nitrate-Nitrite
560 µg/L 5.6%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BREWSTER, JEB
Phone
720-335-7885
Email
[email protected]

Frequently asked questions about Steamboat Ii Md

Is Steamboat Ii Md tap water safe to drink?

EPA monitoring detected 19 contaminants in Steamboat Ii Md's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Steamboat Ii Md's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Steamboat Ii Md serve?

Steamboat Ii Md reports serving 1,450 people in Colorado, per its EPA record.

Has Steamboat Ii Md had any water quality violations?

The EPA has 439 violations on file for Steamboat Ii Md, of which 18 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.