← Colorado

Tap water quality report

Rocky Ford City of

EPA monitoring tested this supplier for 108 contaminants and detected 28. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
28
detected
4,443
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Otero

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
336
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
Other Monitoring Resolved 2015-07-01
Other Monitoring Resolved 2015-07-01

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0085 µg/L 2/2 2025
PFHXS 0.0060 µg/L 2/2 2025
PFOS 0.0041 µg/L 1/2 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
74.525 µg/L 93%
of the EPA limit 80 µg/L
worst single sample: 86.3 µg/L
64/64 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
19.82 µg/L 33%
of the EPA limit 60 µg/L
worst single sample: 21.7 µg/L
59/59 SYR4 2012–2019
Bromodichloromethane
20.38 µg/L
No EPA limit set
worst single sample: 29.1 µg/L
34/34 SYR4 2012–2019
Bromoform
19.045 µg/L
No EPA limit set
worst single sample: 26.1 µg/L
34/34 SYR4 2012–2019
Dibromochloromethane
27.715 µg/L
No EPA limit set
worst single sample: 31.1 µg/L
34/34 SYR4 2012–2019
Chloroform
11.48 µg/L
No EPA limit set
worst single sample: 17.4 µg/L
33/34 SYR4 2012–2019
Dibromoacetic Acid
11.15 µg/L
No EPA limit set
worst single sample: 11.3 µg/L
26/26 SYR4 2015–2019
Dichloroacetic Acid
4.85 µg/L
No EPA limit set
worst single sample: 7.8 µg/L
22/26 SYR4 2015–2019
Nitrate
3140 µg/L 31%
of the EPA limit 10000 µg/L
worst single sample: 3200 µg/L
22/22 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Monobromoacetic Acid
1.55 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
16/26 SYR4 2015–2019
Trichloroacetic Acid
4.695 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
12/26 SYR4 2015–2019
Monochloroacetic Acid
10.22 µg/L
No EPA limit set
worst single sample: 11.1 µg/L
9/26 SYR4 2015–2019
Fluoride
962.5 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L
6/6 SYR4 2012–2019
Nitrate-Nitrite
1475 µg/L 15%
of the EPA limit 10000 µg/L
worst single sample: 1500 µg/L
6/6 SYR4 2012–2016
Barium
67.4 µg/L 3.4%
of the EPA limit 2000 µg/L
worst single sample: 70 µg/L
5/5 SYR4 2013–2019
Selenium
14.7 µg/L 29%
of the EPA limit 50 µg/L
worst single sample: 16 µg/L
5/5 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
7.064 pCi/L 47%
of the EPA limit 15 pCi/L
worst single sample: 7.94 pCi/L
4/5 SYR4 2013–2019
Combined Uranium
19.8 µg/L 66%
of the EPA limit 30 µg/L
worst single sample: 20 µg/L
3/5 SYR4 2013–2019
Combined Radium (-226 And -228)
0.3900 pCi/L 7.8%
of the EPA limit 5 pCi/L
worst single sample: 0.4000 pCi/L
2/2 SYR4 2013
Lithium
48 µg/L
No EPA limit set
2/2 UCMR-5 2025
Cadmium
0.2000 µg/L 4%
of the EPA limit 5 µg/L
1/5 SYR4 2013–2019
Nitrite
42 µg/L 4.2%
of the EPA limit 1000 µg/L
1/6 SYR4 2012–2016
Thallium, Total
0.8400 µg/L 42%
of the EPA limit 2 µg/L
1/5 SYR4 2013–2019
Xylenes, Total
0.8200 µg/L 0%
of the EPA limit 10000 µg/L
1/11 SYR4 2012–2019
80 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LONG, RICK
Phone
719-469-2666
Email
[email protected]

Frequently asked questions about Rocky Ford City of

Is Rocky Ford City of tap water safe to drink?

EPA monitoring detected 28 contaminants in Rocky Ford City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Rocky Ford City of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Rocky Ford City of serve?

Rocky Ford City of reports serving 4,443 people in Colorado, per its EPA record.

Has Rocky Ford City of had any water quality violations?

The EPA has 336 violations on file for Rocky Ford City of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.