Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-12-01 → 2023-12-31 |
| TT | Health-based | Resolved | 2023-12-01 → 2023-12-31 |
| TT | Health-based | Resolved | 2023-12-01 → 2023-12-31 |
| TT | Health-based | Resolved | 2023-12-01 → 2023-12-31 |
| TT | Health-based | Resolved | 2023-11-01 → 2023-11-30 |
| TT | Health-based | Resolved | 2023-11-01 → 2023-11-30 |
| TT | Health-based | Resolved | 2023-11-01 → 2023-11-30 |
| TT | Health-based | Resolved | 2023-11-01 → 2023-11-30 |
| TT | Health-based | Resolved | 2016-05-01 |
| TT | Health-based | Resolved | 2016-05-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 629.35 µg/L 63% of the EPA limit 1000 µg/L
worst single sample: 710 µg/L | 84/99 | SYR4 | 2012–2019 |
| TTHM | 93.6 µg/L 117% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 113 µg/L | 57/57 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 51.6 µg/L 86% of the EPA limit 60 µg/L
worst single sample: 78.66 µg/L | 56/57 | SYR4 | 2012–2019 |
| Bromodichloromethane | 27.38 µg/L No EPA limit set
worst single sample: 31.8 µg/L | 39/39 | SYR4 | 2012–2019 |
| Chloroform | 69.87 µg/L No EPA limit set
worst single sample: 75.4 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.4 µg/L No EPA limit set
worst single sample: 8.5 µg/L | 38/39 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 23.1 µg/L No EPA limit set
worst single sample: 34.99 µg/L | 35/36 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 29.1745 µg/L No EPA limit set
worst single sample: 34.1 µg/L | 34/36 | SYR4 | 2015–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 26/26 | LCR | 2025 |
| Nitrate | 3390 µg/L 34% of the EPA limit 10000 µg/L
worst single sample: 3400 µg/L | 22/28 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.8 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 21/36 | SYR4 | 2015–2019 |
| Fluoride | 724 µg/L 18% of the EPA limit 4000 µg/L
worst single sample: 780 µg/L | 17/20 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.1 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 17/36 | SYR4 | 2015–2019 |
| Combined Radium (-226 And -228) | 1.3 pCi/L 26% of the EPA limit 5 pCi/L
worst single sample: 1.5 pCi/L | 11/11 | SYR4 | 2014–2019 |
| Dalapon | 1.82 µg/L 0.9% of the EPA limit 200 µg/L
worst single sample: 1.9 µg/L | 9/28 | SYR4 | 2012–2019 |
| Barium | 95.45 µg/L 4.8% of the EPA limit 2000 µg/L
worst single sample: 107 µg/L | 8/9 | SYR4 | 2012–2019 |
| Bromoform | 0.8500 µg/L No EPA limit set
worst single sample: 0.9000 µg/L | 6/39 | SYR4 | 2012–2019 |
| Lithium | 61.2 µg/L No EPA limit set | 6/6 | UCMR-5 | 2024 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 3/9 | SYR4 | 2012–2019 |
| Combined Uranium | 1.95 µg/L 6.5% of the EPA limit 30 µg/L
worst single sample: 2 µg/L | 2/3 | SYR4 | 2013–2015 |
| Gross Alpha, Excl. Radon And U | 1.9385 pCi/L 13% of the EPA limit 15 pCi/L
worst single sample: 1.96 pCi/L | 2/3 | SYR4 | 2013–2015 |
| Carbon Tetrachloride | 0.5000 µg/L 10% of the EPA limit 5 µg/L | 1/10 | SYR4 | 2012–2019 |
| Chromium | 2 µg/L 2% of the EPA limit 100 µg/L | 1/9 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 6.67 µg/L No EPA limit set | 1/36 | SYR4 | 2015–2019 |
| Nitrate-Nitrite | 1400 µg/L 14% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2012 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Wellington Town of
Is Wellington Town of tap water safe to drink?
EPA monitoring detected 25 contaminants in Wellington Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wellington Town of's water?
EPA monitoring detected Chlorite, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Wellington Town of serve?
Wellington Town of reports serving 11,720 people in Colorado, per its EPA record.
Has Wellington Town of had any water quality violations?
The EPA has 115 violations on file for Wellington Town of, of which 16 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.