Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MON | Monitoring | Resolved | 2016-06-01 → 2016-06-30 |
| MON | Monitoring | Resolved | 2016-06-01 → 2016-06-30 |
| MON | Monitoring | Resolved | 2016-06-01 → 2016-06-30 |
| MR | Monitoring | Resolved | 2016-04-01 → 2016-06-30 |
| MR | Monitoring | Resolved | 2016-04-01 → 2016-06-30 |
| MR | Monitoring | Resolved | 2016-04-01 → 2016-06-30 |
| Other | Monitoring | Resolved | 2006-07-01 |
| Other | Monitoring | Resolved | 2006-07-01 |
| MR | Monitoring | Resolved | 2005-01-01 → 2007-12-31 |
| MR | Monitoring | Resolved | 2005-01-01 → 2007-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2000 µg/L 20% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0012 mg/L 8% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Nitrate-Nitrite | 1919.5 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 2000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 180.6 µg/L 9% of the EPA limit 2000 µg/L
worst single sample: 181 µg/L | 3/3 | SYR4 | 2013–2019 |
| Selenium | 9 µg/L 18% of the EPA limit 50 µg/L
worst single sample: 9.2 µg/L | 3/3 | SYR4 | 2013–2019 |
| Chromium | 19.805 µg/L 20% of the EPA limit 100 µg/L
worst single sample: 20.4 µg/L | 2/3 | SYR4 | 2013–2019 |
| Fluoride | 183.85 µg/L 4.6% of the EPA limit 4000 µg/L
worst single sample: 184 µg/L | 2/3 | SYR4 | 2013–2019 |
| Arsenic | 0.9000 µg/L 9% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.6900 pCi/L 14% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2019 |
| Combined Uranium | 1.9 µg/L 6.3% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2019 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Old Homestead Mhp
Is Old Homestead Mhp tap water safe to drink?
EPA monitoring detected 10 contaminants in Old Homestead Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Old Homestead Mhp's water?
EPA monitoring detected Nitrate, Lead, Nitrate-Nitrite, Barium, Selenium, and others. The full list with the level and data source for each is above.
How many people does Old Homestead Mhp serve?
Old Homestead Mhp reports serving 120 people in Colorado, per its EPA record.
Has Old Homestead Mhp had any water quality violations?
The EPA has 267 violations on file for Old Homestead Mhp, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.