Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Archived | 2026-01-01 → 2026-03-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-03-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-03-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-03-31 |
| Other | Monitoring | Resolved | 2007-07-01 |
| Other | Monitoring | Resolved | 2007-07-01 |
| Other | Monitoring | Resolved | 2006-07-01 |
| Other | Monitoring | Resolved | 2006-07-01 |
| Other | Monitoring | Resolved | 2003-07-01 |
| Other | Monitoring | Resolved | 2003-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 39.625 µg/L 50% of the EPA limit 80 µg/L
worst single sample: 44.3 µg/L | 32/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 28.7 µg/L 48% of the EPA limit 60 µg/L
worst single sample: 33.3 µg/L | 32/32 | SYR4 | 2012–2019 |
| Nitrate | 140 µg/L 1.4% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0016 mg/L 11% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Bromodichloromethane | 5.425 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 4/4 | SYR4 | 2012–2018 |
| Chloroform | 25.565 µg/L No EPA limit set
worst single sample: 28.1 µg/L | 4/4 | SYR4 | 2012–2018 |
| Combined Uranium | 1.19 µg/L 4% of the EPA limit 30 µg/L
worst single sample: 1.2 µg/L | 2/2 | SYR4 | 2013–2015 |
| Dibromochloromethane | 1.463 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 2/4 | SYR4 | 2012–2018 |
| Dichloroacetic Acid | 6.09 µg/L No EPA limit set
worst single sample: 6.1 µg/L | 2/2 | SYR4 | 2018 |
| Gross Alpha, Excl. Radon And U | 0.7000 pCi/L 4.7% of the EPA limit 15 pCi/L | 2/2 | SYR4 | 2013–2015 |
| Trichloroacetic Acid | 5.78 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 2/2 | SYR4 | 2018 |
| Barium | 54 µg/L 2.7% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2014 |
| Combined Radium (-226 And -228) | 0.2000 pCi/L 4% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
| Fluoride | 120 µg/L 3% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2014 |
| Monochloroacetic Acid | 2.4 µg/L No EPA limit set | 1/2 | SYR4 | 2018 |
| Nitrate-Nitrite | 140 µg/L 1.4% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2014 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Gunnison County Wsd
Is Gunnison County Wsd tap water safe to drink?
EPA monitoring detected 16 contaminants in Gunnison County Wsd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Gunnison County Wsd's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Gunnison County Wsd serve?
Gunnison County Wsd reports serving 800 people in Colorado, per its EPA record.
Has Gunnison County Wsd had any water quality violations?
The EPA has 17 violations on file for Gunnison County Wsd, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.