Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2008-09-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2008-09-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2008-09-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2008-07-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2008-07-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 2008-07-01 → 2008-09-30 |
| MR | Monitoring | Resolved | 1999-04-01 → 1999-04-30 |
| MR | Monitoring | Resolved | 1999-04-01 → 1999-04-30 |
| MR | Monitoring | Resolved | 1999-04-01 → 1999-04-30 |
| MR | Monitoring | Resolved | 1998-10-01 → 1998-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2023 |
| TTHM | 36.1 µg/L 45% of the EPA limit 80 µg/L
worst single sample: 41.2 µg/L | 18/18 | SYR4 | 2012–2019 |
| Nitrate | 290 µg/L 2.9% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 13.875 µg/L 23% of the EPA limit 60 µg/L
worst single sample: 15 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.74 µg/L No EPA limit set
worst single sample: 10.3 µg/L | 15/15 | SYR4 | 2013–2019 |
| Chloroform | 13.7 µg/L No EPA limit set
worst single sample: 15.1 µg/L | 15/15 | SYR4 | 2013–2019 |
| Dibromochloromethane | 6.27 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 15/15 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.145 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 12/12 | SYR4 | 2015–2019 |
| Dichloroacetic Acid | 5.78 µg/L No EPA limit set
worst single sample: 6 µg/L | 12/12 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 4.245 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 12/12 | SYR4 | 2015–2019 |
| Bromoform | 0.9320 µg/L No EPA limit set
worst single sample: 1 µg/L | 9/15 | SYR4 | 2013–2019 |
| Arsenic | 1.2825 µg/L 13% of the EPA limit 10 µg/L
worst single sample: 1.3 µg/L | 2/2 | SYR4 | 2016–2019 |
| Barium | 41.4 µg/L 2.1% of the EPA limit 2000 µg/L
worst single sample: 42 µg/L | 2/2 | SYR4 | 2016–2019 |
| Fluoride | 275 µg/L 6.9% of the EPA limit 4000 µg/L
worst single sample: 280 µg/L | 2/2 | SYR4 | 2016–2019 |
| Monochloroacetic Acid | 3.135 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 2/12 | SYR4 | 2015–2019 |
| Combined Radium (-226 And -228) | 0.8000 pCi/L 16% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2018 |
| Combined Uranium | 1.1 µg/L 3.7% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2018 |
| Gross Alpha, Excl. Radon And U | 0.6630 pCi/L 4.4% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2018 |
| Nitrate-Nitrite | 290 µg/L 2.9% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2018 |
| Selenium | 0.5100 µg/L 1% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2016–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Winter Park Ranch Wsd
Is Winter Park Ranch Wsd tap water safe to drink?
EPA monitoring detected 20 contaminants in Winter Park Ranch Wsd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Winter Park Ranch Wsd's water?
EPA monitoring detected Lead, TTHM, Nitrate, Total Haloacetic Acids (HAA5), Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Winter Park Ranch Wsd serve?
Winter Park Ranch Wsd reports serving 3,250 people in Colorado, per its EPA record.
Has Winter Park Ranch Wsd had any water quality violations?
The EPA has 15 violations on file for Winter Park Ranch Wsd, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.