← Colorado

Tap water quality report

Granby Town of North Service Area

EPA monitoring tested this supplier for 77 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
15
detected
2,025
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Grand

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
15
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2025-06-20
Other Monitoring Resolved 2025-06-20
Other Monitoring Resolved 2025-06-20
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2024-10-01
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30
MR Monitoring Resolved 2015-07-01 → 2015-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
1002.5 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L
34/34 SYR4 2012–2019
TTHM
82.08 µg/L 103%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 91.1 µg/L
33/33 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
38.815 µg/L 65%
of the EPA limit 60 µg/L
worst single sample: 46.3 µg/L
31/32 SYR4 2012–2019
Bromodichloromethane
8.9 µg/L
No EPA limit set
worst single sample: 10.1 µg/L
21/21 SYR4 2012–2019
Chloroform
75.8 µg/L
No EPA limit set
worst single sample: 86.8 µg/L
21/21 SYR4 2012–2019
Dichloroacetic Acid
13.88 µg/L
No EPA limit set
worst single sample: 18.2 µg/L
19/19 SYR4 2015–2019
Trichloroacetic Acid
26.617 µg/L
No EPA limit set
worst single sample: 27.28 µg/L
18/19 SYR4 2015–2019
Lead
0.0080 mg/L 53%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Dibromochloromethane
1.24 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
13/21 SYR4 2012–2019
Monochloroacetic Acid
1.572 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
3/19 SYR4 2015–2019
Nitrate
87 µg/L 0.9%
of the EPA limit 10000 µg/L
2/16 SYR4 2012–2019
Barium
25 µg/L 1.3%
of the EPA limit 2000 µg/L
1/1 SYR4 2019
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
1/1 SYR4 2019
Combined Radium (-226 And -228)
4.2 pCi/L 84%
of the EPA limit 5 pCi/L
1/1 SYR4 2019
Selenium
4 µg/L 8%
of the EPA limit 50 µg/L
1/1 SYR4 2019
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BELLATTY, DOUGLAS A
Email
[email protected]

Frequently asked questions about Granby Town of North Service Area

Is Granby Town of North Service Area tap water safe to drink?

EPA monitoring detected 15 contaminants in Granby Town of North Service Area's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Granby Town of North Service Area's water?

EPA monitoring detected Fluoride, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Granby Town of North Service Area serve?

Granby Town of North Service Area reports serving 2,025 people in Colorado, per its EPA record.

Has Granby Town of North Service Area had any water quality violations?

The EPA has 15 violations on file for Granby Town of North Service Area, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.