Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2019-10-01 → 2019-12-31 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2000 µg/L 20% of the EPA limit 10000 µg/L
worst single sample: 2400 µg/L | 100/112 | SYR4 | 2012–2019 |
| TTHM | 54 µg/L 68% of the EPA limit 80 µg/L
worst single sample: 57.2 µg/L | 41/48 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17.735 µg/L No EPA limit set
worst single sample: 18.5 µg/L | 32/43 | SYR4 | 2012–2019 |
| Bromoform | 6.875 µg/L No EPA limit set
worst single sample: 7.8 µg/L | 32/43 | SYR4 | 2012–2019 |
| Dibromochloromethane | 21.955 µg/L No EPA limit set
worst single sample: 24 µg/L | 32/43 | SYR4 | 2012–2019 |
| Barium | 246 µg/L 12% of the EPA limit 2000 µg/L
worst single sample: 260 µg/L | 29/29 | SYR4 | 2012–2019 |
| Fluoride | 1640 µg/L 41% of the EPA limit 4000 µg/L
worst single sample: 1900 µg/L | 29/29 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 29/29 | LCR | 2025 |
| Combined Radium (-226 And -228) | 5.355 pCi/L 107% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.5 pCi/L | 28/28 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 18.935 µg/L 32% of the EPA limit 60 µg/L
worst single sample: 20.7 µg/L | 22/24 | SYR4 | 2012–2019 |
| Chloroform | 9.3 µg/L No EPA limit set | 21/43 | SYR4 | 2012–2019 |
| Combined Uranium | 24.35 µg/L 81% of the EPA limit 30 µg/L
worst single sample: 31 µg/L | 20/22 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 16.191 pCi/L 108% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 27.23 pCi/L | 20/20 | SYR4 | 2012–2019 |
| Arsenic | 3.86 µg/L 39% of the EPA limit 10 µg/L
worst single sample: 4.1 µg/L | 17/29 | SYR4 | 2012–2019 |
| Selenium | 4.08 µg/L 8.2% of the EPA limit 50 µg/L
worst single sample: 6.4 µg/L | 17/29 | SYR4 | 2012–2019 |
| Lithium | 29.5 µg/L No EPA limit set | 14/14 | UCMR-5 | 2025 |
| Nitrate-Nitrite | 2115 µg/L 21% of the EPA limit 10000 µg/L
worst single sample: 2500 µg/L | 12/13 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.855 µg/L No EPA limit set
worst single sample: 8.9 µg/L | 10/10 | SYR4 | 2015–2019 |
| Dichloroacetic Acid | 5.75 µg/L No EPA limit set
worst single sample: 5.9 µg/L | 6/10 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 3.375 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 6/10 | SYR4 | 2015–2019 |
| Nitrite | 111 µg/L 11% of the EPA limit 1000 µg/L
worst single sample: 120 µg/L | 3/13 | SYR4 | 2012–2019 |
| Hexachlorocyclopentadiene | 0.0640 µg/L 0.1% of the EPA limit 50 µg/L
worst single sample: 0.0650 µg/L | 2/44 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1 µg/L No EPA limit set | 2/10 | SYR4 | 2015–2019 |
| Monochloroacetic Acid | 10.4 µg/L No EPA limit set
worst single sample: 10.7 µg/L | 2/10 | SYR4 | 2015–2019 |
| Toluene | 4.43 µg/L 0.4% of the EPA limit 1000 µg/L
worst single sample: 4.6 µg/L | 2/47 | SYR4 | 2012–2019 |
| Antimony, Total | 2.3 µg/L 38% of the EPA limit 6 µg/L | 1/29 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.8600 µg/L 14% of the EPA limit 6 µg/L | 1/43 | SYR4 | 2013–2019 |
| Hexachlorobenzene | 0.0076 µg/L 0.8% of the EPA limit 1 µg/L | 1/44 | SYR4 | 2013–2019 |
77 contaminants tested, none detected
Utility contact
Frequently asked questions about Pinery Wwd
Is Pinery Wwd tap water safe to drink?
EPA monitoring detected 32 contaminants in Pinery Wwd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pinery Wwd's water?
EPA monitoring detected Nitrate, TTHM, Bromodichloromethane, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Pinery Wwd serve?
Pinery Wwd reports serving 12,901 people in Colorado, per its EPA record.
Has Pinery Wwd had any water quality violations?
The EPA has 327 violations on file for Pinery Wwd, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.