← Colorado

Tap water quality report

Hasty Water Authority

EPA monitoring tested this supplier for 77 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
14
detected
244
people served
86
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Bent

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

86
health-based violations
192
violations on file
5
still open
ViolationTypeStatusPeriod
MCL Health-based Addressed 2026-04-01 → 2026-06-30
MCL Health-based Addressed 2026-04-01 → 2026-06-30
MCL Health-based Addressed 2026-04-01 → 2026-06-30
TT Health-based Unaddressed 2025-09-18
TT Health-based Unaddressed 2025-09-18
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0100 mg/L 67%
of the EPA limit 0.0150 mg/L
28/28 LCR 2026
Combined Radium (-226 And -228)
5.67 pCi/L 113%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 5.7 pCi/L
7/7 SYR4 2013–2019
TTHM
1.65 µg/L 2.1%
of the EPA limit 80 µg/L
worst single sample: 1.7 µg/L
3/3 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
4.584 µg/L 7.6%
of the EPA limit 60 µg/L
worst single sample: 4.86 µg/L
3/3 SYR4 2012–2018
Arsenic
5 µg/L 50%
of the EPA limit 10 µg/L
2/2 SYR4 2016–2019
Barium
27.95 µg/L 1.4%
of the EPA limit 2000 µg/L
worst single sample: 28 µg/L
2/2 SYR4 2016–2019
Bromoform
1.675 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
2/4 SYR4 2012–2018
Fluoride
1139.5 µg/L 28%
of the EPA limit 4000 µg/L
worst single sample: 1140 µg/L
2/2 SYR4 2016–2019
Selenium
14.35 µg/L 29%
of the EPA limit 50 µg/L
worst single sample: 15 µg/L
2/2 SYR4 2016–2019
Chromium
3 µg/L 3%
of the EPA limit 100 µg/L
1/2 SYR4 2016–2019
Dibromoacetic Acid
2.1 µg/L
No EPA limit set
1/2 SYR4 2015–2018
Gross Alpha, Excl. Radon And U
16 pCi/L 107%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
1/1 SYR4 2019
Monochloroacetic Acid
1.37 µg/L
No EPA limit set
1/2 SYR4 2015–2018
Xylenes, Total
0.6000 µg/L 0%
of the EPA limit 10000 µg/L
1/9 SYR4 2012–2019
63 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitrateNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
RATCLIFF, CODY
Phone
719-688-1970
Email
[email protected]

Frequently asked questions about Hasty Water Authority

Is Hasty Water Authority tap water safe to drink?

EPA monitoring detected 14 contaminants in Hasty Water Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hasty Water Authority's water?

EPA monitoring detected Lead, Combined Radium (-226 And -228), TTHM, Total Haloacetic Acids (HAA5), Arsenic, and others. The full list with the level and data source for each is above.

How many people does Hasty Water Authority serve?

Hasty Water Authority reports serving 244 people in Colorado, per its EPA record.

Has Hasty Water Authority had any water quality violations?

The EPA has 192 violations on file for Hasty Water Authority, of which 86 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.