EPA monitoring tested this supplier for 110 contaminants and detected 28. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
28
detected
533,407
people served
4
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Arapahoe

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
17
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MCL Health-based Resolved 2011-01-01 → 2011-01-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31
MR Monitoring Resolved 2016-01-01 → 2016-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0078 µg/L 1/12 2024
PFBS 0.0033 µg/L 1/12 2024
Pfhxa 0.0056 µg/L 1/12 2024
Pfpea 0.0072 µg/L 1/12 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
33.86 µg/L 42%
of the EPA limit 80 µg/L
worst single sample: 76.24 µg/L
518/518 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
31.815 µg/L 53%
of the EPA limit 60 µg/L
worst single sample: 56.6 µg/L
518/518 SYR4 2012–2019
Chlorite
630 µg/L 63%
of the EPA limit 1000 µg/L
worst single sample: 840 µg/L
224/228 SYR4 2012–2019
Bromodichloromethane
8.92 µg/L
No EPA limit set
worst single sample: 11.4 µg/L
91/91 SYR4 2012–2019
Chloroform
24.175 µg/L
No EPA limit set
worst single sample: 35.3 µg/L
90/91 SYR4 2012–2019
Dibromochloromethane
10.2 µg/L
No EPA limit set
worst single sample: 11.5 µg/L
90/91 SYR4 2012–2019
Dibromoacetic Acid
5.5675 µg/L
No EPA limit set
worst single sample: 6.29 µg/L
86/86 SYR4 2018–2019
Dichloroacetic Acid
19.25 µg/L
No EPA limit set
worst single sample: 25.4 µg/L
86/86 SYR4 2018–2019
Trichloroacetic Acid
10.4 µg/L
No EPA limit set
worst single sample: 13.7 µg/L
84/86 SYR4 2018–2019
Bromoform
4.799 µg/L
No EPA limit set
worst single sample: 5.19 µg/L
64/91 SYR4 2012–2019
Fluoride
974.5 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 1070 µg/L
38/38 SYR4 2012–2019
Nitrate
1212.5 µg/L 12%
of the EPA limit 10000 µg/L
worst single sample: 1250 µg/L
36/94 SYR4 2012–2019
Barium
56.72 µg/L 2.8%
of the EPA limit 2000 µg/L
worst single sample: 58.7 µg/L
19/19 SYR4 2012–2019
Lead
0.0025 mg/L 17%
of the EPA limit 0.0150 mg/L
19/19 LCR 2025
Nitrate-Nitrite
1167.5 µg/L 12%
of the EPA limit 10000 µg/L
worst single sample: 1200 µg/L
14/31 SYR4 2012–2019
Chromium
2.365 µg/L 2.4%
of the EPA limit 100 µg/L
worst single sample: 2.5 µg/L
11/19 SYR4 2012–2019
Arsenic
1.46 µg/L 15%
of the EPA limit 10 µg/L
worst single sample: 1.48 µg/L
6/19 SYR4 2012–2019
Monochloroacetic Acid
1.224 µg/L
No EPA limit set
worst single sample: 1.24 µg/L
5/86 SYR4 2018–2019
Selenium
6.736 µg/L 13%
of the EPA limit 50 µg/L
worst single sample: 6.82 µg/L
5/19 SYR4 2012–2019
Lithium
21.4 µg/L
No EPA limit set
5/12 UCMR-5 2024
Combined Uranium
4.87 µg/L 16%
of the EPA limit 30 µg/L
worst single sample: 5.2 µg/L
3/3 SYR4 2017
Combined Radium (-226 And -228)
3.89 pCi/L 78%
of the EPA limit 5 pCi/L
worst single sample: 4 pCi/L
2/2 SYR4 2017
Gross Alpha, Excl. Radon And U
0.8750 pCi/L 5.8%
of the EPA limit 15 pCi/L
worst single sample: 0.9000 pCi/L
2/3 SYR4 2017
Mercury
0.0290 µg/L 1.5%
of the EPA limit 2 µg/L
1/13 SYR4 2012–2019
82 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WILKINSON, EARL
Phone
303-739-7544
Email
[email protected]

Frequently asked questions about Aurora City of

Is Aurora City of tap water safe to drink?

EPA monitoring detected 28 contaminants in Aurora City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Aurora City of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Chlorite, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Aurora City of serve?

Aurora City of reports serving 533,407 people in Colorado, per its EPA record.

Has Aurora City of had any water quality violations?

The EPA has 17 violations on file for Aurora City of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.