← California

Tap water quality report

Wheatland Park Estates

EPA monitoring tested this supplier for 41 contaminants and detected 6. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

41
contaminants tested
6
detected
26
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Yuba

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
13
violations on file
1
still open
ViolationTypeStatusPeriod
Other Monitoring Addressed 2021-07-01
MR Monitoring Resolved 2021-01-01 → 2021-12-31
MR Monitoring Resolved 2021-01-01 → 2021-12-31
MR Monitoring Resolved 2019-10-01
MR Monitoring Resolved 2019-10-01
MR Monitoring Resolved 2018-06-01
MR Monitoring Resolved 2018-06-01
MR Monitoring Resolved 2013-06-01
MR Monitoring Resolved 2013-06-01
MR Monitoring Resolved 2013-01-01 → 2013-01-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2880 µg/L 29%
of the EPA limit 10000 µg/L
14/14 SYR4 2013–2019
Lead
0.0324 mg/L 216%
above the EPA limit of 0.0150 mg/L
3/3 LCR 2023
Barium
66.2 µg/L 3.3%
of the EPA limit 2000 µg/L
1/1 SYR4 2016
Cadmium
2.8 µg/L 56%
of the EPA limit 5 µg/L
1/1 SYR4 2016
Nitrate-Nitrite
2520 µg/L 25%
of the EPA limit 10000 µg/L
1/1 SYR4 2016
Nitrite
0.1500 µg/L 0%
of the EPA limit 1000 µg/L
1/2 SYR4 2016–2019
35 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4-DAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCopperCarbon TetrachlorideChromiumDichloromethaneDiquatEndothallEthylbenzeneFluorideGlyphosateMercurySeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BIRKENSTOCK, JASON
Phone
916-269-9288
Email
[email protected]

Frequently asked questions about Wheatland Park Estates

Is Wheatland Park Estates tap water safe to drink?

EPA monitoring detected 6 contaminants in Wheatland Park Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wheatland Park Estates's water?

EPA monitoring detected Nitrate, Lead, Barium, Cadmium, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Wheatland Park Estates serve?

Wheatland Park Estates reports serving 26 people in California, per its EPA record.

Has Wheatland Park Estates had any water quality violations?

The EPA has 13 violations on file for Wheatland Park Estates, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.