Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1999-01-01 → 1999-01-31 |
| MCL | Health-based | Resolved | 1999-01-01 → 1999-01-31 |
| MR | Monitoring | Archived | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2010-12-01 → 2010-12-31 |
| MR | Monitoring | Resolved | 2008-01-01 → 2008-01-31 |
| MR | Monitoring | Resolved | 2008-01-01 → 2008-01-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 8.85 µg/L No EPA limit set
worst single sample: 10.3 µg/L | 62/62 | SYR4 | 2012–2019 |
| Bromoform | 46.815 µg/L No EPA limit set
worst single sample: 79 µg/L | 62/62 | SYR4 | 2012–2019 |
| Dibromochloromethane | 22.38 µg/L No EPA limit set
worst single sample: 25.9 µg/L | 62/62 | SYR4 | 2012–2019 |
| TTHM | 74.195 µg/L 93% of the EPA limit 80 µg/L
worst single sample: 114 µg/L | 62/62 | SYR4 | 2012–2019 |
| Chloroform | 4.8 µg/L No EPA limit set
worst single sample: 6 µg/L | 61/62 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 16 µg/L 27% of the EPA limit 60 µg/L
worst single sample: 21 µg/L | 60/62 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 12.4 µg/L No EPA limit set
worst single sample: 15 µg/L | 53/62 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 49/49 | LCR | 2024 |
| Dichloroacetic Acid | 4 µg/L No EPA limit set | 41/62 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3 µg/L No EPA limit set
worst single sample: 4 µg/L | 25/62 | SYR4 | 2012–2019 |
| Nitrate | 795 µg/L 8% of the EPA limit 10000 µg/L
worst single sample: 800 µg/L | 22/28 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 2 µg/L No EPA limit set | 14/62 | SYR4 | 2012–2019 |
| Lithium | 78.5 µg/L No EPA limit set | 8/8 | UCMR-5 | 2023 |
| Fluoride | 285 µg/L 7.1% of the EPA limit 4000 µg/L
worst single sample: 300 µg/L | 4/5 | SYR4 | 2012–2018 |
| Selenium | 5.7 µg/L 11% of the EPA limit 50 µg/L
worst single sample: 6 µg/L | 4/5 | SYR4 | 2012–2018 |
| Barium | 52.88 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 53.2 µg/L | 3/5 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 570000 µg/L 5700% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 600000 µg/L | 3/5 | SYR4 | 2012–2018 |
| Combined Uranium | 13.22 µg/L 44% of the EPA limit 30 µg/L
worst single sample: 13.4398 µg/L | 2/2 | SYR4 | 2012–2015 |
| Monochloroacetic Acid | 7.85 µg/L No EPA limit set
worst single sample: 8 µg/L | 2/62 | SYR4 | 2012–2019 |
| Copper | 70 µg/L 5.4% of the EPA limit 1300 µg/L | 1/5 | SYR4 | 2012–2018 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L | 1/5 | SYR4 | 2012–2018 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Pleasant Valley Mutual Water Co
Is Pleasant Valley Mutual Water Co tap water safe to drink?
EPA monitoring detected 26 contaminants in Pleasant Valley Mutual Water Co's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pleasant Valley Mutual Water Co's water?
EPA monitoring detected Bromodichloromethane, Bromoform, Dibromochloromethane, TTHM, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Pleasant Valley Mutual Water Co serve?
Pleasant Valley Mutual Water Co reports serving 5,000 people in California, per its EPA record.
Has Pleasant Valley Mutual Water Co had any water quality violations?
The EPA has 7 violations on file for Pleasant Valley Mutual Water Co, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.