Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-08-01 → 2015-08-31 |
| MCL | Health-based | Resolved | 2015-08-01 → 2015-08-31 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-12-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| Other | Monitoring | Resolved | 2012-12-01 |
| Other | Monitoring | Resolved | 2012-12-01 |
| MR | Monitoring | Resolved | 1997-01-01 → 1997-01-31 |
| MR | Monitoring | Resolved | 1997-01-01 → 1997-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 7070 µg/L 71% of the EPA limit 10000 µg/L
worst single sample: 15390.6 µg/L | 768/770 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 7542.5 µg/L 75% of the EPA limit 10000 µg/L
worst single sample: 15400 µg/L | 306/307 | SYR4 | 2012–2018 |
| TTHM | 53.482 µg/L 67% of the EPA limit 80 µg/L
worst single sample: 70.64 µg/L | 103/124 | SYR4 | 2012–2019 |
| Chloroform | 46.117 µg/L No EPA limit set
worst single sample: 64.24 µg/L | 94/125 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 41.385 µg/L 69% of the EPA limit 60 µg/L
worst single sample: 51.9 µg/L | 82/124 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 19.9 µg/L No EPA limit set
worst single sample: 23.6 µg/L | 81/124 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 22.665 µg/L No EPA limit set
worst single sample: 27.2 µg/L | 80/124 | SYR4 | 2012–2019 |
| Bromodichloromethane | 5.2435 µg/L No EPA limit set
worst single sample: 7.14 µg/L | 74/125 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.6635 µg/L No EPA limit set
worst single sample: 5.84 µg/L | 64/125 | SYR4 | 2012–2019 |
| Bromoform | 3.124 µg/L No EPA limit set
worst single sample: 3.19 µg/L | 45/125 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 30/30 | LCR | 2023 |
| Arsenic | 10 µg/L 100% of the EPA limit 10 µg/L
worst single sample: 12 µg/L | 27/27 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.85 µg/L No EPA limit set
worst single sample: 2 µg/L | 11/124 | SYR4 | 2012–2019 |
| Combined Uranium | 6.3176 µg/L 21% of the EPA limit 30 µg/L
worst single sample: 6.854 µg/L | 10/10 | SYR4 | 2014–2019 |
| Fluoride | 134 µg/L 3.4% of the EPA limit 4000 µg/L
worst single sample: 140 µg/L | 7/20 | SYR4 | 2012–2019 |
| Nitrite | 0.0900 µg/L 0% of the EPA limit 1000 µg/L | 5/307 | SYR4 | 2012–2018 |
| Barium | 110 µg/L 5.5% of the EPA limit 2000 µg/L | 3/20 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.81 µg/L No EPA limit set
worst single sample: 4 µg/L | 3/124 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2 µg/L No EPA limit set | 2/124 | SYR4 | 2012–2019 |
| 1,2-DIBROMO-3-CHLOROPROPANE | 0.0110 µg/L 5.5% of the EPA limit 0.2000 µg/L | 1/21 | SYR4 | 2013–2019 |
| Chromium | 10 µg/L 10% of the EPA limit 100 µg/L | 1/20 | SYR4 | 2012–2019 |
| Lithium | 9.7 µg/L No EPA limit set | 1/4 | UCMR-5 | 2024 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Modesto - Salida
Is City of Modesto - Salida tap water safe to drink?
EPA monitoring detected 22 contaminants in City of Modesto - Salida's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Modesto - Salida's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, TTHM, Chloroform, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does City of Modesto - Salida serve?
City of Modesto - Salida reports serving 14,537 people in California, per its EPA record.
Has City of Modesto - Salida had any water quality violations?
The EPA has 23 violations on file for City of Modesto - Salida, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.